Service Manual LEX Series Indoor Units Outdoor Units LEX 7 ONG 7 LEX 9 ONG 9 LEX 12 ONG 12 LEX 14 ONG 14 REFRIGERANT R410A COOLING ONLY HEAT PUMP JANUARY - 2006 CONTENT...
Page 2
LIST OF EFFECTIVE PAGES LIST OF EFFECTIVE PAGES Note: Changes in the pages are indicated by a “Revision#” in the footer of each effected page (when none indicates no changes in the relevant page). All pages in the following list represent effected/ non effected pages divided by chapters.
INTRODUCTION INTRODUCTION General The new LEX split wall mounted range comprise the ST (cooling only) and RC (heat pump) models, as follows: Cooling Only LEX 7ST, LEX 9ST, LEX 12ST, LEX 14ST. • Heat Pump LEX 7RC, LEX 9RC, LEX 12RC, LEX 14RC. •...
INTRODUCTION Indoor Unit The indoor unit is wall mounted, and can be easily fitted to many types of residential and commercials applications. It includes: Casing with air inlet and outlet grills. • A large-diameter tangential fan. • Bended coil with treated aluminum fins. •...
Service valves” flare” type connection. • Interconnecting wiring terminal block. • Fresh air motor for LEX 7-14 (optional). • Tubing Connections Flare type interconnecting tubing to be produced on site. For further details please refer to the Installation Manual, APPENDIX A.S...
Page 7
INTRODUCTION 1.11 Matching Table 1.11.1 R410A INDOOR UNITS OUTDOOR UNITS MODEL REFRIGER. LEX7 LEX9 LEX12 LEX14 PXD9 PXD12 PXD15 ONG7 ST R410A √ ONG9 ST R410A √ √ √ ONG12 ST R410A √ √ √ ONG14 ST R410A √ √ √...
PRODUCT DATA SHEET PRODUCT DATA SHEET LEX 7 R410A Specification Model Indoor Unit LEX-7 Model Outdoor Unit ONG-7 Installation Method of Pipe Flared Characteristics Cooling Heating Units Cooling Only 7230 7400 Btu/hr 7230 Capacity 2.12 2.12 2.17 0.63 0.595 0.63 Power input 3.37...
Page 9
PRODUCT DATA SHEET LEX 9 R410A Specification Model Indoor Unit LEX-9 Model Outdoor Unit ONG-9 Installation Method of Pipe Flared Characteristics Units Cooling Only Cooling Heating Btu/hr 9280 9280 9890 Capacity 2.72 2.72 2.90 0.825 0.849 Power input 0.825 3.30 3.42 EER (Cooling) or COP(Heating) 3.30...
Page 10
PRODUCT DATA SHEET LEX 12 R410A Specification Model Indoor Unit LEX-12 Model Outdoor Unit ONG-12 Installation Method of Pipe Flared Characteristics Units Cooling Only Cooling Heating 12210 14160 Btu/hr 12210 Capacity 3.58 3.58 4.15 1.112 1.112 1.145 Power input 3.22 3.62 3.22 EER (Cooling) or COP(Heating)
Page 11
PRODUCT DATA SHEET LEX 14 R410A Specification Model Indoor Unit LEX-14 Model Outdoor Unit ONG-14 Installation Method of Pipe Flared Characteristics Cooling Heating Units Cooling Only Btu/hr 14400 14400 15010 Capacity 4.22 4.22 4.40 1.31 1.310 1.31 Power input 3.22 3.36 3.22 EER (Cooling) or COP(Heating)
RATING CONDITIONS RATING CONDITIONS Standard conditions in accordance with ISO 5151, ISO 13253 (for ducted units) and EN 14511. Cooling: Indoor: C DB 19 C WB Outdoor: 35 C DB Heating: Indoor: C DB Outdoor: 7 C DB 6 C WB Operating Limits 3.1.1 R410A Indoor...
Page 14
PERFORMANCE DATA & PRESSURE CURVES PERFORMANCE DATA & PRESSURE CURVES LEX7 / ONG7 R410A 5.1.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. Entering Air DB Entering Air WB/DB ID Coil( Data OD Coil( 15/21 17/24 19/27 21/29...
PERFORMANCE DATA & PRESSURE CURVES 5.1.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL( ENTERING WB OD COIL( 1.13 0.48 1.09 0.51 1.04 0.53 1.21 0.49 1.17 0.51 1.13 0.54 1.29 0.49 1.25...
PERFORMANCE DATA & PRESSURE CURVES LEX9 / ONG9 R410A 5.4.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. Entering Air DB Entering Air WB/DB ID Coil( Data OD Coil( 15/21 17/24 19/27 21/29 23/32 2.87 2.97 3.04 3.11...
Page 19
PERFORMANCE DATA & PRESSURE CURVES 5.4.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL( ENTERING WB OD COIL( 1.52 0.68 1.46 0.72 1.41 0.76 1.64 0.70 1.58 0.73 1.52 0.77 1.74 0.70 1.68...
Page 21
PERFORMANCE DATA & PRESSURE CURVES 5.6.2 Heating. Suction Pressure VS.Outdoor Temp 12.0 11.0 10.0 15 DB (ºC) 20 DB (ºC) 25 DB (ºC) Outdoor Temp.( WB Discharge Pressure VS.Outdoor Temp 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) Outdoor Temp.( WB Revision Y06-01 Service Manual - LEX CONTENT...
Page 22
PERFORMANCE DATA & PRESSURE CURVES LEX12 / ONG12 R410A 5.7.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. Entering Air DB Entering Air WB/DB ID Coil( Data OD Coil( 15/21 17/24 19/27 21/29 23/32 3.77 3.91 4.00 4.10...
Page 23
PERFORMANCE DATA & PRESSURE CURVES 5.7.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL( ENTERING WB OD COIL( 2.18 0.92 2.10 0.98 2.01 1.02 2.34 0.94 2.26 0.99 2.18 1.04 2.49 0.95 2.41...
Page 25
PERFORMANCE DATA & PRESSURE CURVES 5.9.2 Heating. Suction Pressure VS.Outdoor Temp 11.0 10.0 15 DB (ºC) 20 DB (ºC) 25 DB (ºC) Outdoor Temp.( WB Discharge Pressure VS.Outdoor Temp 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) Outdoor Temp.( WB 5-12 Revision Y06-01 Service Manual - LEX...
Page 26
PERFORMANCE DATA & PRESSURE CURVES 5.10 LEX14 / ONG14 R410A 5.10.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. Entering Air DB Entering Air WB/DB ID Coil( Data OD Coil( 15/21 17/24 19/27 21/29 23/32 4.45 4.61 4.72...
Page 27
PERFORMANCE DATA & PRESSURE CURVES 5.10.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL( ENTERING WB OD COIL( 2.31 0.90 2.22 0.96 2.13 1.01 2.49 0.93 2.40 0.98 2.31 1.03 2.64 0.94 2.55...
ELECTRICAL DATA ELECTRICAL DATA Single Units MODEL LEX 7 LEX 9 To indoor To outdoor To indoor To outdoor Power Supply 1PH-230V-50Hz 1PH-230V-50Hz Max Current, (A) Circuit Breaker,(A) 10.0 10.0 Power Supply Wiring. 3 x 1.5 mm 3 x 1.5 mm (No.
CONTROL SYSTEM CONTROL SYSTEM LEX 7-14 LED BASIC MODEL 12.1 Electronic Control 12.1.1 Introduction The electronic control information is designed for service applications, and is common to the following groups of air-conditioners: • ST/ RC group -Cooling only / cooling and heating by heat pump.
Page 41
CONTROL SYSTEM 12.2 Legend - Alternate Current - Air-Conditioner - ON or OFF status CLOCK - ON/OFF Operation Input, (dry contact) COMP - Compressor - Central Processing Unit ELUM - Extended Louver Upward Movement (Software Jumper) E²PROM, EEP - Erase Enable Programmable Read Only Memory - Heating Element - High Pressure Control - Hardware...
CONTROL SYSTEM 12.4 General functions 12.4.1 COMP operation For each Mode including POWER OFF & SB, a Min time delay of 3 min before COMP restarting, excluding DEICING Mode The Min operation time of COMP under different operating conditions is Min operation time of Operation Mode COMP...
Page 43
CONTROL SYSTEM 12.4.5 Protections • High pressure protection is applicable to all operating modes. • Deicing control is valid in Heat and Auto Heat Mode only. • Defrosting control is valid in Dry, Cool, Heat and Auto Modes. • No reset after protection modes. 12.4.6 Thermistors operation •...
Page 44
CONTROL SYSTEM 12.4.6.2 Cases for disabling thermistor short/disconnected detection The detection of thermistor faults (a) and (b) above, are disabled when Deicer Protection is started. The detection will be enabled again only after (1) the deicing is completed, and (2) COMP has been restarted and operated for 30 sec.
Page 45
CONTROL SYSTEM 12.5 Cooling Mode - General Room Temperature, RT, is detected by • RAT in normal operation, or • RCT (R/C sensor) in I-FEEL mode. The resolution of RT is 1 • RT is activating COMP/WVL if (RT > SPT), and •...
Page 46
CONTROL SYSTEM 12.5.1 Cooling Mode: Cool, Auto (at Cooling) Temp: Selected desired temperature. Fan: HIGH, MED, LOW Timer: Any I Feel: On or Off Control function Maintains room temp at desired level by comparing RT and SPT. (RT - SPT) [ COMP (WVL) OFAN...
Page 47
CONTROL SYSTEM 12.5.2 Cooling with Autofan Mode: Cool, Auto (at cooling) Temp: Selected desired temperature Fan: Auto Timer: Any I Feel: On or Off Control function Maintains room temp at desired level and controls the IFAN speed for optimal comfort. (RT - SPT) [ COMP (WVL)
CONTROL SYSTEM 12.6 Heating Mode 12.6.1 Heating Mode - General • In heating Mode, temp. compensation schedule will be activated for wall mounted units. Add to SPT SPT [ I-FEEL ON I-FEEL OFF 18 ≤ SPT ≤ 27 27 < SPT ≤ 30 Notes : •...
Page 49
CONTROL SYSTEM 12.6.3 HE operation • For all Groups, HE can be ON only when IFAN is ON. • For all Groups, HE switches to OFF when ICT > 50 c, and is activated again when ICT ≤ 45 • In SH or RC group, HE operation is limited by the following graph: General : ICT [...
Page 50
CONTROL SYSTEM 12.6.4 Heating, RC or SH Group Mode: Heat, Auto (at heating) Temp: Selected desired temperature Fan: HIGH, MED, LOW Timer: Any I Feel: On or Off Control function Maintains room temp. at desired level by comparing RAT or RCT to SPT. (RT - SPT) [ COMP (WVL)
Page 51
CONTROL SYSTEM 12.6.5 Heating, RC or SH Group with Autofan Mode: Heat, Auto (at heating) Temp: Selected desired temperature Fan: Auto Timer: Any I Feel: On or Off Control function Maintains room temp at desired level by controlling COMP, IFAN and OFAN. (RT - SPT) [ COMP (WVL)
Page 52
CONTROL SYSTEM 12.6.6 OFAN operation is controlled by the graph below when 1. (RAT ≥ SPT – 2 c), AND 2. (ICT ≥ 45 c), AND 3. (COMP is ON) Otherwise, OFAN runs together with COMP. OCT [ OFAN Service Manual - LEX Revision Y06-01 12-13 CONTENT...
Page 53
CONTROL SYSTEM 12.7 Automatic Cooling or Heating 12.7.1 Automatic Cooling or Heating - General • Switching-temperature between Cooling and Heating is SPT ± 3 • Autofan in Automatic Cooling and Heating Mode will activate “Cooling with Autofan Mode” and “Heating with Autofan Mode” respectively. •...
Page 54
CONTROL SYSTEM 12.7.2 Auto Cooling or Heating, RC or SH Groups Mode: Auto Temp: Selected desired temperature Fan: Timer: Any I Feel: On or Off Control function Maintains room temp at desired level by selecting between cooling and heating modes. (RT - SPT) [ Auto Heat Mode Auto Cool Mode...
CONTROL SYSTEM 12.8 Dry Mode 12.8.1 Dry, ST or RC group Mode: Dry Temp: Selected desired temp Fan: Low (automatically selected by software) Timer: Any I FEEL: Control function Reduce room humidity with minimum temp. fluctuations by operating in Cool Mode with low speed IFAN.
Page 56
CONTROL SYSTEM 12.9 Protection 12.9.1 Cooling Mode Protections Indoor Coil Defrost Mode: Cooling, Dry, Auto Temp: Selected desired temp. Fan: Timer: Any I Feel: On or Off Control Function Protect the indoor coil from ice formation at low ambient temperature. ICT [ OFAN COMP...
Page 57
CONTROL SYSTEM 12.3.2 High Pressure Protection Mode: (Auto) Cooling or Dry Temp: Selected desired temp. Fan: Timer: Any I Feel: On or Off Control Function To protect the COMP from the high pressure built-up in the outdoor coil during normal cooling operation, by switching OFF the IFAN and COMP.
Page 58
CONTROL SYSTEM 12.9.3 Heating Mode Protections Outdoor coil Deicing (excluding RH Group) Mode: Heating, Auto (at heating) Temp: Selected desired Temp Fan: Timer: Any I FEEL: Control function Protects the Outdoor coil from ice formation by controlling COMP & RV operation. Scope This new deicer is designed to operate at extreme temp conditions.
Page 59
CONTROL SYSTEM Deicing procedure OCT [ (DDT) 3 min 3 min max 12 min. COMP DI (note 1) DI (note 2) OFAN IFAN is forced to Low Speed IFAN HEs are forced ON IFAN Note 3 HEs are forced OFF OPER BLINK Notes :...
Page 60
CONTROL SYSTEM 12.9.4 High pressure protection (excluding RH Group) Mode: (Auto) Heating Fan: Timer: Any I Feel: On or Off Control Function Protect the Compressor from high pressure by switching OFF the OFAN and COMP. ICT [ For all models except WAX For WAX model COMP is forced OFF COMP...
Page 61
CONTROL SYSTEM 12.10 Timer Mode: Any Temp. Selected desired temp Fan: Timer: Timer On, Timer Off I Feel: On or Off Control function • Starts or stops the unit operation after pre-set time. If RC-1 is used, the timer setting will be (0.5 - 24 Hr) from the moment the timer is set. The minimum resolution is 30 minutes.
CONTROL SYSTEM 12.11 Forced Operation Forced operation allows units to start, stop and operate in Cooling or Heating in pre-set temperature according to the following table: Pre-set Temp for : Forced operation mode WMF, WMN, WNG models Cooling 22°C Heating 28°C Note: •...
CONTROL SYSTEM 12.12 Sleep Mode Mode: Any Temp: Set – desired temperature selected Fan: Timer: Interact with Sleep Timer as described in sect 12.2 I Feel: On or Off The Sleep mode is activated by using the sleep button on the R/C. In Sleep Mode, the unit will automatically adjust the SPT to turn up/down the room temperature (RT) gradually to provide maximum comfort to the user in sleep.
Page 64
CONTROL SYSTEM 12.12.2 Time adjustment in Sleep Mode The user can make use of the Off-Timer to extend the Sleep Time from 7 hours to 12 hour (max). The operation of the new “Extended Sleep Mode” is illustrated by the graphs below.
Page 65
CONTROL SYSTEM 12.13 Clogged Air Filter Filter LED ON after 512 HR. Filter LED is turned OFF, and the Filter Timer is restarted by pressing the reset button. 12-26 Revision Y06-01 Service Manual - LEX CONTENT...
Page 66
CONTROL SYSTEM 12.14 Controller Self-Test Procedure 12.14.1 By Shorting Test Jumper J1 SELF-TEST FLOW CHART FOR CONTROLLER (VERSION 4V5 OR HIGHER) SHORT JUMPER Step 1 RC/ST TEST (CONTROL PCB) MODEL CONFIGURATION TEST PRESS ON Step 2 POWER STEP MOTOR TEST BUTTON FREQUENCY TEST...
Page 67
CONTROL SYSTEM 12.14.2 By Remote Control Settings: 1: TURNING ON THE POWER. Turn ON the power, make sure that the unit is in operation. STEP 2 : ENABLE SELF-TEST MODE • Use the remote control to send the first settings to display / indoor unit HEAT mode, HIGH IFAN, set temperature to 16 ºC, no I-FEEL Sleep or any other timer settings are needed.
Page 68
CONTROL SYSTEM STEP 4 : AUTO LED WALK TEST. • All the LEDS will turn OFF. • All the LEDS will turn ON for 1 second one by one in the following sequence: STAND-BY OPERATE TIMER FILTER COOL HEAT. • In PRX all the LEDS will turn ON for 1 second one by one in the following sequence : 18 °c 20 °c...
Page 69
CONTROL SYSTEM Fail condition: 0 sec - STAND-BY is turned ON 3 sec - STAND-BY, OPER, TIMER and FILTER are turned ON • When the timing reset test is completed, the next test will start automatically. STEP 9: MEMORY TEST (EEPROM) •...
Page 70
CONTROL SYSTEM 12.15 On Unit Indicators and Controls Lights up when the Air Conditioner is connected to power and STAND BY ready to receive the R/C commands INDICATOR Blinks continuously in case of any thermistor failure. Lights up during operation. Blinks for 300 ms, to announce that a R/C infrared signal has been received and stored.
Page 71
CONTROL SYSTEM 12.16 Clock Random Delay From 0 to 2.5 seconds Clock Switch Open Clock Switch close The Clock is activate according to the following table: A/C STATE CLOCK STATE CLOCK ACTION A/C NEW STATE (clock is changed) (after clock is changed) before clock is changed) before clock is changed) OFF by...
Page 72
CONTROL SYSTEM 12.17 System Diagnostics Pressing Mode button for 5-10 seconds in SB or any other operation mode will activate diagnostic mode by the acknowledgment of 3 short beeps and lighting of COOL and HEAT LEDs. In diagnostic mode, system problems will be indicated by blinking of Heat & Cool LEDs.
Page 73
CONTROL SYSTEM 12B. CONTROL SYSTEM LEX 7-14 LED FULLY FEATURED 12B.1 General Functions 12B.1.1 Operation Modes Auto Mode Cooling Mode Drying Mode Fan Mode Heating Mode 12B.1.2 Functions I FEEL, Forced Mode, Protection - hot keep, Deicing, defrosting, Timer, Sleep,...
Page 74
CONTROL SYSTEM 12B.2 Operation Modes 12B.2.1 Auto Mode Operation Heating / Fan Drying Cooling 22ºC 26ºC If RT >= 26ºC - A/C will go into Cooling Mode; Initial SPT is 25ºC. If 22ºC < RT < 26ºC- A/C go into Drying mode; Initial SPT is 24ºC. If RT <= 22ºC - A/C will go into Heating Mode;...
Page 75
CONTROL SYSTEM 12B.2.3 Comp’ Operation COMP SPT-1ºC SPT+1ºC If RT >= SPT+1ºC, COMP and OFAN is activated; If RT <= SPT-1ºC, COMP stop, OFAN will turn off after 5 seconds delay. Note: COMP turns off have 3 min delay protection; COMP turn on have 5 min continues protection.
Page 76
CONTROL SYSTEM High Pressure Protection (Excluding cooling only unit type) 12B.2.5 OCT (ºC) >= 3 min COMP Any OFAN follows COMP OFAN FORCED ON OFAN Any IFAN Any If (OCT >= 61ºC), IFAN is forced to LOW. If (OCT <= 55ºC), IFAN restore to normal.
Page 77
CONTROL SYSTEM 12B.2.7 Drying Mode SPT range: 16ºC~30ºC. Initial: 24ºC; IFAN speed range: Auto, Low, Mid and Hi. Initial speed: Low; IFAN speed can be changed only in state (1); State SPT-1ºC SPT SPT+2ºC SPT+3ºC If in state (1) - (SPT - 1ºC < RT <= SPT + 2ºC), unit will go into state (2) If in state (1) or state (2), - (RT <= SPT - 1ºC), unit will go into state (3) If in state (3), - (SPT <= RT <...
Page 78
CONTROL SYSTEM 12B.2.8 Heating Mode SPT range: 16ºC~30ºC. Initial: 24ºC; In wall mounted units the indoor RT compensation temp’ value is - 3ºC -> RT, (Excluding I FEEL Mode) IFAN speed range: Auto, Low, Mid and Hi. Initial speed: Low; Auto Fan IFAN SPT-4ºC SPT-3ºC SPT-2ºC SPT-1ºC...
Page 79
CONTROL SYSTEM 12B.2.10 Hot keep function COMP on, IFAN set speed Supper low 21ºC 23ºC 32ºC 38ºC Note: If COMP is on for a period of 4 minutes or (ICT >= 38ºC), IFAN is in set speed; COMP off, IFAN set speed Supper low 21ºC...
Page 80
CONTROL SYSTEM 12B.2.12 High Pressure Protection ICT (ºC) >= 10s >= 3 Min COMP Any OFAN Any If ICT >= 61ºC, OFAN turn off. If ICT <= 55ºC, OFAN turn on. If (ICT >= 66ºC) for duration of 10 seconds, COMP turn off. If ICT <= 52ºC, COMP turn on.
Page 81
CONTROL SYSTEM 12B.2.14 Deicing Deicing starts, if OCT <= -6ºC and meets with one of the following conditions: ICT < 39ºC, and IFAN is on for 20 minutes, and COMP is on for 5 minutes, and that ICT decrease 1ºC per 6 minutes, occur 3 times; ICT <...
Page 82
CONTROL SYSTEM 12B.3 Other Functions 12B.3.1 Sleep Function Cooling or drying Mode SPT + 2ºC SPT + 1ºC Standby Heating Mode SPT - 2ºC SPT - 3ºC 1 hour 1 hour 6 hours After 8 hours, it will go into Standby. Note: During sleep mode, IFAN speed can be set by RC command.
Page 83
CONTROL SYSTEM 12B.3.3 I FEEL The switchover between RCT by the remote controller and RT detected by the control board can be done by “I FEEL” function. After receiving the “I FEEL” command from the remote controller, MCU decide the operation mode of the air-conditioner by RCT detected by the remote controller.
Page 84
CONTROL SYSTEM Louvers control 12B.3.7 Louvers is effective only if IFAN operates, but the remote controller can control its “ON” and “OFF” at any time after start up. When the air-conditioner is energized initially, the louvers is off, the following two modes can be controlled: (1) swing continuously;...
Page 85
CONTROL SYSTEM Sound Indication 12B.3.10 The buzzer will beep twice when starts and a long sound when stops, one sound for receiving a command. Emergency Function 12B.3.11 The first press on the emergency key on the indoor control board, the unit enters to cooling mode (SPT: 22ºC;...
Page 86
CONTROL SYSTEM 12B.3.15 Protection When all relays meet their function requirements at the same time, there should be an interval of 0.5 second between every two relays. The action procedures are as follows: ON state: AHEAT Æ RV Æ OFAN —> COMP OFF state: AHEAT Å...
Page 87
CONTROL SYSTEM 12B.3.19 Self-test When shorting the TEST jumper, the action will be per 1 second according to following: beep one -> Cool led on-> Cool led off, Heat led on-> Heat led off, power led on-> power led off ,running led on-> running led off, timer led on-> timer led off ,filter led on->...
TROUBLESHOOTING TROUBLESHOOTING SYMPTON PROBABLE CAUSE CORRECTIVE ACTION The stand-by There is no correct voltage -If the voltage is low repair power indicator (red led) between the line and neutral supply. on the central terminals on main P.C.B control display -If there is no voltage repair panel doesn’t light general wiring.
Page 89
TROUBLESHOOTING SYMPTON PROBABLE CAUSE CORRECTIVE ACTION No cooling or Outdoor fan motor faulty or -Replace P.C.B. heating only other fault caused, compressor -Outdoor fan blocked remove indoor fan works. overload protection cut out. obstructions. Only indoor fan Outdoor fan blocked. -Remove obstructions.
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.2 Indoor Unit LEX 7, 9, 12, 14 LED Qty. Description Grill A Assy./LEX7/9/12/14 AIRWELL . 465800009 465800016 Grill A Assy./ Electra LEX 7/9/12/14 465800020 Grill A Assy./ LEX7/9/12/14 Bosch Grill A Assy./ LEX7/9/12/14 Siemens...
Page 91
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.3 Outdoor Unit ONG 7, 9, 12 ST Service Manual - LEX Revision Y06-01 14-3 CONTENT...
Page 92
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.4 Outdoor Unit ONG 7 ST Drawing Code Item Desc Quantity Number Effective From Effective To 433218 Front Panel A 05-Mar-04 Active 433221 Air Inlet Ring-420 05-Mar-04 Active 433223 Painting Insulation Plate 05-Mar-04 Active 4519251 Axial Fan OD=400 05-Mar-04...
Page 93
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.5 Outdoor Unit ONG 9 ST Drawing Item Code Item Desc Quantity Number Effective From Effective To 433218 Front Panel A 05-Mar-04 Active 433219 Front Panel A1 05-Mar-04 05-Mar-04 433221 Air Inlet Ring-420 05-Mar-04 Active 433223 Painting Insulation Plate...
Page 94
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.6 Outdoor Unit ONG 12 ST Drawing Item Code Item Desc Quantity Number Effective From Effective To 433218 Front Panel A 15-Nov-03 13-Jan-04 433219 Front Panel A1 13-Jan-04 Active 433221 Air Inlet Ring-420 15-Nov-03 Active 433223 Painting Insulation Plate...
Page 95
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.7 Outdoor Unit ONG 14 ST Service Manual - LEX Revision Y06-01 14-7 CONTENT...
Page 96
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.8 Outdoor Unit ONG 14 ST Drawing Effective Item Code Item Desc Quantity Number Effective From 433219 Front Panel A1 01-Mar-04 15-Mar-04 433218 Front Panel A 15-Mar-04 Active 433221 Air Inlet Ring-420 01-Mar-04 Active 433223 Painting Insulation Plate 01-Mar-04...
Page 97
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.9 Outdoor Unit ONG 7 RC Service Manual - LEX Revision Y06-01 14-9 CONTENT...
Page 98
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.10 Outdoor Unit ONG 7 RC Drawing Item Code Item Desc Quantity Number Effective From Effective To 433218 Front Panel A 05-Mar-04 Active 433219 Front Panel A1 05-Mar-04 05-Mar-04 433221 Air Inlet Ring-420 05-Mar-04 Active 433223 Painting Insulation Plate...
Page 99
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.11 Outdoor Unit ONG 9,12 RC Service Manual - LEX Revision Y06-01 14-11 CONTENT...
Page 100
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.12 Outdoor Unit ONG 9 RC Drawing Item Code Item Desc Quantity Number Effective From Effective To 433218 Front Panel A 05-Mar-04 Active 433219 Front Panel A1 05-Mar-04 05-Mar-04 433221 Air Inlet Ring-420 05-Mar-04 Active 433223 Painting Insulation Plate...
Page 101
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.13 Outdoor Unit ONG 12 RC Drawing Item Code Item Desc Quantity Number Effective From Effective To 433218 Front Panel A 05-Mar-04 Active 433219 Front Panel A1 05-Mar-04 05-Mar-04 433221 Air Inlet Ring-420 05-Mar-04 Active 433223 Painting Insulation Plate...
Page 102
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.14 Outdoor Unit ONG 14 RC 14-14 Revision Y06-01 Service Manual - LEX CONTENT...
Page 103
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.15 Outdoor Unit ONG 14 RC Drawing Effective Item Code Item Desc Quantity Number Effective From 433219 Front Panel A1 23-Feb-04 15-Mar-04 433218 Front Panel A 15-Mar-04 Active 433221 Air Inlet Ring-420 23-Feb-04 Active 433223 Painting Insulation Plate 23-Feb-04...
OPTIONAL ACCESSORIES OPTIONAL ACCESSORIES 15.1 RCW Wall Mounted Remote Control 15.1.1 The RCW wall mounted remote control can be fitted to a large range and models, It can be used as IR (wirless mode) or wired controler. the RCW can control up to15 indoor units using the same settings (on its wired aplication), The max wiring length between the controller to the last indoor unit is 300m.
Page 105
OPTIONAL ACCESSORIES 15.2 RCW2 Wall Mounted Remote Cntrol 15.2.1 The RCW2 wall mounted remote controler is a wired controler that can provide affective controling management up to 15 different settings and temp’ zones. The RCW2 can be connected up to a max’ of 32 units,allowing a max wiring length of 1000m.
Page 106
OPTIONAL ACCESSORIES 15.3 RCW/RCW2 Wiring Connections as Shown on Kit Service Manual - LEX Revision Y06-01 15-3 CONTENT...
APPENDIX A APPENDIX A INSTALLATION AND OPERATION MANUAL ► OPERATION MANUAL LEX 7,9,12,14 LED ► INSTALLATION MANUAL LEX 7,9,12,14 LED Service Manual - LEX Revision Y06-01 16-1 CONTENT...