A.6

Limiting the mains current consumption

If your mains fusing is below 16 A, the current consumption can be reduced in steps from 16 A to 8 A.
The maximum heating power is reduced correspondingly. Here, take into consideration whether other
loads are connected to the same fused circuit or whether your ECO thermostat is the only load.
Basic setup
Acoustic signal
Display
Autostart
Resolution
Curr.Consumpt. 16.0A
DLK connected
‫סּ‬
ESC
OK
Curr.Consumpt.
Max: 16.00
Min:
8.00
16.00
‫סּ‬
ESC
OK
By pressing
(ESC) you are returned to the menu level without any change.
A.7

Entering the offset of the displayed temperature (calibration)

Deviations to the calibrated reference thermometers (e.g. LAUDA DigiCal) can be corrected internally
by the "Offset" function.
Calibration
Calibration
Factory calibration
‫סּ‬
ESC
OK
Temp. ref. meas. device
Max:28.16
Min:-22.16
25.16
‫סּ‬
ESC
OK
By pressing
84
on►
The adjacent menu window appears.
Standby
Standby
.
The adjacent menu window appears.
Standby
The entry window appears. The value indicated on the refer-
ence thermometer must be entered as the value.
+/-
(ESC) you are returned to the menu level without any change.
Appendix with settings
Access to the main menu level is obtained by pressing the
enter key
.
Selection and confirmation of
Basic
setup.
As well as
Curr.Consumpt.
Select
Curr.Consumpt.
Change the value with
Single figures can be selected by pressing
Confirm the input with the enter key
Access to the main menu level is obtained by pressing the
enter key
.
Selection and confirmation of
Select
Calibration
with
Change the value with
Single figures can be selected by pressing
By pressing
(+/-) the arithmetic sign can be changed.
You confirm the set value by pressing
Setup
the set value is displayed.
with
.
or .
or .
.
Setup
Calibration.
or
and confirm with
or .
or .
.