Digital Input; B List Of "Alarm And Warning Codes - Lauda E 4 G Operating Instructions Manual

Heating and cooling thermostats with control head gold
Hide thumbs Also See for E 4 G:
Table of Contents

Advertisement

B
List of "Alarm and warning codes"
Alarms
Alarm code
Low Level Pump
1
2
Low Level Pump
3
Overtemperature
4
Pump blocked
5
Connection Command
9
T ext Pt100
T ext analog
10
11
T ext serial
12
Input Analog 1
13
Input Analog 2
15

Digital Input

Warnings
Code 0XX Control sys-
tem
1
CAN receive overf
2
Watchdog Reset
3
T_il limit active
4
T_ih limit active
5
corrupt parameter
6
corrupt progr
7
Invalid Parameter
8
CAN system
9
Unknown Modul
10
SW control too old
11
SW safety too old
12
SW command too
old
13
SW cool too old
14
SW analog too old
15
SW serial too old
16
SW contact old
17
SW Valve 0 old
18
SW Valve 1 old
19
SW Valve 2 old
20
SW Valve 3 old
21
SW Valve 4 old
26
SW HTC old
27
SW Ext Pt100 old
33
RTC wrong data
41
wrong net voltage
42
no eco type
43
no eco voltage
44
chiller missing
45
Diff.voltages
86
Meaning
Pump runs too fast (low level)
Low level in the float
Overtemperature (T > Tmax)
Pump blocked (standstill)
Remote control unit command triggered in running operation
External Pt100 actual value is not present.
External analog actual value is not present.
External serial actual value is not present.
Analog module: Current interface 1, interruption.
Analog module: Current interface 2, interruption.
Error on digital input
Meaning
Overflow during CAN reception
Watchdog reset
til llmit active
tih llmit active
Inadmissible internal parameter
Inadmissible programmer data
Inadmissible parameter in memory
Problem during internal data interchange
Unknown module connected
Software version of control panel too old
Software version of protection too old
Software version of command remote
control unit too old
Software version of cooling module too old
Software version of analog too old
Software version of serial too old
Software version of contact module too old
Software version of solenoid valve too old
Software version of solenoid valve 1 too old
Software version of solenoid valve 2 too old
Software version of solenoid valve 3 too old
Software version of solenoid valve 4 too old
Software version of high temperature cooler
too old
Software version of external Pt100 too old
Internal clock defective
Incorrect mains voltage setting
Device type not configured
Mains voltage not configured
Chiller not running
Different mains voltage configured (head
and cooling underpart)
Appendix with settings
Code 3XX SmartCool
1
CAN receive overf
2
Watchdog Reset
3
adaption missing
4
Pressure switch
activated
5
Clean condenser
6
TO1 out of range
(Klixon)
7
Invalid Parameter
8
CAN system
9
Unknown Modul
10
SW control too old
11
SW safety too old
12
SW command too
old
13
SW cool too old
14
SW analog too old
15
SW serial too old
16
SW contact old
17
SW Valve 0 old
18
SW Valve 1 old
19
SW Valve 2 old
20
SW Valve 3 old
21
SW Valve 4 old
26
SW HTC old
27
SW Ext Pt100 old
33
valve sm0 break
34
valve sm1 break
35
valve sm2 break
36
valve sm3 break
37
output sm0
38
output sm1
39
output sm2
40
output sm3
41
sm0 min too small
42
no eco type
43
no eco voltage
44
chiller missing
ECO GOLD
Meaning
Overflow during CAN reception
Watchdog reset
No adaption run
Pressure Switch in cooling circuit triggered
Clean condenser
Injection temperature outside value range
Inadmissible parameter in memory
Problem during internal data interchange
Unknown module connected
Software version of control panel too old
Software version of protection too old
Software version of command remote
control unit too old
Software version of cooling module too old
Software version of analog too old
Software version of RS232 too old
Software version of contact module too old
Software version of solenoid valve 0 too old
Software version of solenoid valve 1 too old
Software version of solenoid valve 2 too old
Software version of solenoid valve 3 too old
Software version of solenoid valve 4 too old
Software version of high temperature cooler
too old
Software version of external Pt100 too old
Cable of injection valve 0 defective
Cable of injection valve 1 defective
Cable of injection valve 2 defective
Cable of injection valve 3 defective
Triggering of injection valve 0 defective
Triggering of injection valve 1 defective
Triggering of injection valve 2 defective
Triggering of injection valve 3 defective
Start value of injection valve too small
Device type not configured
Mains voltage not configured
Chiller not running
25/08/2011/ YACE0088