Functions; Operation Functions - Sanyo SAP-KMRV93GJH Technical & Service Manual

Dc inverter multi-system air conditioner
Hide thumbs Also See for SAP-KMRV93GJH:
Table of Contents

Advertisement

8. FUNCTIONS

8-1. Operation Functions

Functions of the main unit controller
1 OFF
: • Used to stop the unit when the remote
(Self-diagnostics)
controller is unavailable.
• Used when service inspection is performed.
2 ON
: • During normal operation: Starts operation
from the remote controller.
• Emergency operation: When the remote
controller is unavailable, moving this switch
from the OFF position to the ON position
starts automatic operation.
3 TEST
: • Used when operating performance are
checked.
• Used when pump-down is carried out.
(Operates at the rated frequency. At this
time, the main unit lamp flashes, and the
remote controller signal cannot be
received.)
4 DEMO
: • This function is for shop displays. Ordinarily
it is not used.
• Used during servicing.
Automatic operation
Operating mode selection
When automatic operation is selected, the indoor and outdoor
temperature sensors function, and either HEAT, DRY, or COOL
mode operation is selected automatically.
Indoor temperature
15°C
(Approx.)
(Approx.)
22°C
20°C
HEAT
mode
18°C
• When multiple indoor units are connected and this unit is
started while another indoor unit is operating, the operating
mode is as shown in the table below.
Operating mode
before change
operating mode
HEAT
COOL
DRY
• If the remote controller is used to start automatic operation, a
differing-mode check is performed if the operating modes are
not the same.
Desired-temperature memory
• The set temperature in the program can be changed as
desired within the range of ±4°C. This temperature can then
be stored. During automatic operation, press the temperature
setting buttons to change the temperature.
Set
temperature
22°C
27°C
(standard)
27°C
COOL
mode
Temperature
DRY
at which
mode
operation
starts
(Range:
20 – 26°C)
24°C
Multi
Operating mode
after change
COOL
DRY
DRY
DRY
HEAT
HEAT
HEAT
HEAT
SENSOR DRY
During automatic operation, the system adjusts the room
temperature and fan speed according to the conditions in the
room, in order to maintain a comfortable room environment.
SENSOR DRY operation
• DRY operation is as shown in the figure below.
Load
COOL zone
A zone
B zone
Conditions are monitored at all
times when the room temperature
is below 15°C.
DRY A
The compressor operation frequency varies depending on the
relative humidity.
The indoor fan operates with 1/f fluctuation.
DRY B
The compressor operates at a low operating frequency.
The indoor fan operates with 1/f fluctuation.
Monitor
• Monitoring operation takes place when the room temperature
is below 15°C.
• When the monitoring range is entered, the compressor stops,
and the indoor fan operates at LL.
PAM-α control
• In order to further improve inverter performance, control is
switched between PWM control at low operation speeds, and
PAM control at high operation speeds, making the most
effective use of power.
26