1-3 TEST RUN CONTROL

1. When the test run signal is transmitted from standard wired, wireless remote controller,
simple remote controller and central remote controller.
(1) The test run operation starts and the electric expansion valve is controlled to a maximum flow, regardless of
the temperature condition.
(2) Frost prevention operation has priority over item(1).
(3) After 60 minutes passes, the test run stops.

2. When the test run signal is transmitted from the outdoor unit.

(1) Whether state of the indoor unit operates or stops, All units in the same refrigerant system will start to conduct a
test run in accordance with the operation mode set by DIP SW 1-1 and SW 1-2 of outdoor unit ( see 1 - 2 - 2 ).
(2) Test running initialization is shown below.
Operating Mode
Fan speed
Room Temperature Indication
Vertical Air Direction Panel
Swing
*ENSAMPLE
1
2
3
COMPACT CASSETTE TYPE
EXCEPT FOR THE DUCT MODEL
Cooling
Hi
18
Position
OFF
4
Heating
Hi
30
1
Position
4
OFF
1
2
3
4
COMPACT WALL MOUNTED TYPE
01-06
DUCT TYPE
Cooling
Hi
18
1
2
3
CEILING TYPE
1
2
3
4
Heating
Hi
30

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents