Outdoor Unit Fan Motor; Check Point : Aj*126L / Aj*126U; Check Point : Aj*A90/72L / Aj*A90/72U - Fujitsu Airstage V series Service Manual

Multi air conditioning system for buildings
Hide thumbs Also See for Airstage V series:
Table of Contents

Advertisement

SERVICE PARTS INFORMATION 12

Outdoor Unit Fan Motor

Check Point : AJ*126L / AJ*126U

Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
BLUE
RED
WHITE
YELLOW
BLACK

Check Point : AJ*A90/72L / AJ*A90/72U

Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
BLUE
RED
WHITE
YELLOW
BLACK
Pr
Pr
Read Wire
Resistance value
82.0
Blue - Red
Red - White
38.5
22.0
Red - Black
Read Wire
Resistance value
59.5
Blue - Red
Red - White
45.0
22.5
Red - Black
06-105
15%
15%
15%
at 20°C
5%
5%
5%
at 20°C