Check Point : Auxb18Latf; Check Point : Auya20 / 25 / 30Ljatf; Check Point : Auya36 / 45 / 54Latf - Fujitsu Airstage V series Service Manual

Multi air conditioning system for buildings
Hide thumbs Also See for Airstage V series:
Table of Contents

Advertisement

Check Point : AUXB18LATF

p Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
(140°C)

Check Point : AUYA20 / 25 / 30LJATF

p Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
(150°C)

Check Point : AUYA36 / 45 / 54LATF

p Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
3
Thermal protector
130°C
Low(Blue)
Med(Violet)
Hi(Red)
(Black)
(AC)
(White)
Low(Blue)
Med(Violet)
Hi(Red)
(Black)
(AC)
(White)
Pr
2
1
(AC)
Read Wire
Resistance value(20 ° C)
White - Red
Red
- Black
Red
- Violet
Violet - Blue
Read Wire
Resistance value(20 ° C)
White - Red
Red
- Black
Red
- Violet
Violet - Blue
Read Wire
Resistance value(20°C)
1
3
2
3
06-100
446 ± 8%
552 ± 8%
117 ± 8%
117 ± 8%
120 ± 8%
55.3 ± 8%
61.2 ± 8%
283 ± 8%
44.5 ± 10%
40.5 ± 10%

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents