4. OUTDOOR UNIT

4-1 INPUT / OUTPUT LIST

Discharge pressure sensor
Suction pressure sensor
Discharge temperature sensor 1
Discharge temperature sensor 2
Discharge temperature sensor 3 (AO126 only) Themistor
Heat exchanger temperature sensor
I
Receiver tanker liquid level (low) sensor
N
Receiver tanker liquid level (mid) sensor
P
Receiver tanker liquid level (high) sensor
U
Sub-cool heat exchanger (outlet) sensor
T
Sub-cool heat exchanger (inlet) sensor
Liquid temperature sensor 1
Liquid temperature sensor 2
Suction temperature sensor
Outdoor temperature sensor
Operation current sensor
Rotary SW & DIP-SW
Compressor 1
Compressor 2
Compressor 3
Fan motor 1 (Hi/Lo/OFF)
Fan motor 2 (Hi/Lo/OFF)
Electronic expansion valve 1
Electronic expansion valve 2
Solenoid valve 1
Solenoid valve 2
O
Solenoid valve 3
U
Solenoid valve 4 (Master unit)
T
Solenoid valve 4 (Slave unit)
P
Solenoid valve 5
U
Solenoid valve 6
T
Solenoid valve 7
Solenoid valve 8-1
Solenoid valve 8-2
Solenoid valve 8-3 (AO126 only)
Crank case heater 1-3
Base heater
External output 1 (CN49) (Error display)
External output 2 (CN48) (Operation display)
Communication
LON WORKS
Inverter communication
Input / Output
External
External input 1 (CN50)
(Remote controller / External priority)
Input / Output
External input 2 (CN52) (Cooling / Heating priority)
External output 1 (CN48) (Operation display)
External output 2 (CN49) (Error display)
LED display
LED 1 to LED 6
Input / output or kind of detail
Pressure sensor
Pressure sensor
Themistor
Themistor
Themistor
Themistor
Themistor
Themistor
Themistor
Themistor
Themistor
Themistor
Themistor
Themistor
Current transformer
Address and function setting
Magnetic relay (Slave unit only)
Magnetic relay
Magnetic relay
Fan motor
Fan motor
EEV coil
EEV coil
Hot gas bypass
Receiver tanker liquid level adjustment
Receiver tanker liquid level detection
Refrigerant flow control
Refrigerant flow control
Receiver tanker gas bypass
Oil adjustment among outdoor unit
Oil adjustment among outdoor unit
Oil return valve
Oil return valve
Oil return valve
Compressor
Field supply
ON (Error) / OFF (Normal)
ON (Operation) / OFF (Stop)
Dry contact input
ON (Operation) / OFF (Stop)
ON (Error) / OFF (Normal)
Display the information on operation, error and setting with LED (1-6)
04-01
Control range
Measure range 0.0 to 5.0MPa
Measure range 0.0 to 5.0MPa
Measure range 10 to 130
Measure range 10 to 130
Measure range 10 to 130
Measure range -35 to 70
Measure range -35 to 70
Measure range -35 to 70
Measure range -35 to 70
Measure range -35 to 70
Measure range -35 to 70
Measure range -35 to 70
Measure range -35 to 70
Measure range -35 to 70
Measure range -20 to 58
Operation coil AC220-240V, 50Hz
Operation coil AC220-240V, 50Hz
Operation coil AC220-240V, 50Hz
AC220-240V, 50Hz
AC220-240V, 50Hz
Operating voltage DC12V
Operating voltage DC12V
AC220-240V, 50Hz, 6W
AC220-240V, 50Hz, 6W
AC220-240V, 50Hz, 6W
AC220-240V, 50Hz, 8W
AC220-240V, 50Hz, 8W
AC220-240V, 50Hz, 8W
AC220-240V, 50Hz, 6W
AC220-240V, 50Hz, 6W
AC220-240V, 50Hz, 6W
AC220-240V, 50Hz, 6W
AC220-240V, 50Hz, 6W
AC240V, 35W
AC220-240V, 35W
Control output: DC 0/12V, Max.15mA
Control output: DC 0/12V, Max.15mA
Control output: DC 0/12V, Max.15mA
Control output: DC 0/12V, Max.15mA