2-3-9 External Switch Controller

1. DIP SW SETTING
(1) MODE setting.
Sets the mode.
SW1-1
SW1-2
OFF
OFF
OFF
ON
OFF
ON
Example :
MODE 0
DIP-SW3-5 : ON
DIP-SW5-5 : OFF
SW1
Contact :ON
Contact :OFF
SW2
Contact :ON
Contact :OFF

(2) Delay-time setting

Set to ON for switching operation mode in 1 minute after contact.
SW1-3
OFF
ON

(3) External switch controller and remote controller, or dual external switch controllers setting

Set the external switch controller DIP switch No.1-4,1-5 according to the following table.
Number of
remote controllers
One controller
Two controllers
(4) Group control setting
Number of indoor unit connection (One/Multiple)
This is switched according to the number of connected indoor units.
DIP-SW1
Number of indoor unit
No.6
OFF
One unit connection
ON
Multiple unit connection
MODE setting
MODE 0
ON
MODE 1
MODE 2
No setting
ON
MODE 1
SW1
Contact :ON
Contact :OFF
P2
P1
(
Factory setting)
Delay-time setting
Instant (200msec)
Delay (1 min)
(
Master controller
DIP-SW1
DIP-SW1
No.4
No.5
OFF
ON
OFF
OFF
(
Factory setting)
This MODE sets to P1 operation mode if SW1 has a contact input of DIP-SW3-5.
This MODE sets to P2 operation mode if SW2 has a contact input of DIP-SW5-5.
This MODE sets to P1 operation mode if a contact of SW1 is switched ON
This MODE sets to P2 operation mode if a contact of SW1 is switched OFF ON.
This MODE sets to P1 operation mode in 1 minute after stop operation if a contact
of SW1 is switched ON
OFF.
This MODE sets to P2 operation mode in 1 minute after stop operation if a contact
of SW1 is switched OFF
ON.
P1
Factory setting)
Slave controller
DIP-SW1
DIP-SW1
No.4
No.5
ON
ON
02-33
(
Detail
MODE 2
SW1
Contact :ON
Contact :OFF
P2
ST
*
1 : ST means "Stop operation".
*
2 : If the indoor unit is operated between
ST and P1 or ST and P2,
it may not be set at the operational
status of P1 or P2.
Indoor unit
Indoor unit
1 2 3
controller
1 2 3
Master controller
Master controller Slave controller
One controller
Two controllers
Factory setting)
OFF.
P1
ST
P2
*
*
2
2
controller
1 2 3
1 2 3
1 2 3