Indoor Unit Fan Motor; Check Point : Abya12 / 14Latf; Check Point : Abya18Latf; Check Point : Abya24Latf - Fujitsu Airstage V series Service Manual

Multi air conditioning system for buildings
Hide thumbs Also See for Airstage V series:
Table of Contents

Advertisement

SERVICE PARTS INFORMATION 11

Indoor Unit Fan Motor

Check Point : ABYA12 / 14LATF

p Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
(150°C)

Check Point : ABYA18LATF

p Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
(150°C)

Check Point : ABYA24LATF

p Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
(150°C)
Low(Blue)
Med(Violet)
Hi(Red)
(Black)
(AC)
(White)
Low(Blue)
Med(Violet)
Hi(Red)
(Black)
(AC)
(White)
Low(Blue)
Med(Violet)
Hi(Red)
(Black)
(AC)
(White)
06-98
Read Wire
Resistance value(20 ° C)
White - Red
Red
- Black
Red
- Violet
Violet - Blue
Read Wire
Resistance value(20 ° C)
White - Red
Red
- Black
Red
- Violet
Violet - Blue
Read Wire
Resistance value(20 ° C)
White - Red
Red
- Black
Red
- Violet
Violet - Blue
252 ± 8%
337 ± 8%
59.5 ± 8%
59.5 ± 8%
134 ± 8%
243 ± 8%
63.1 ± 8%
63.1 ± 8%
110 ± 8%
181 ± 8%
64.9 ± 8%
64.9 ± 8%