Test Run; Finishing; Customer Guidance - Fujitsu ASUH15LPAS Installation Manual

Wall-mounted type
Table of Contents

Advertisement

Setting
Function number
value
30
31
(For cooling)
(For heating)
■ Room temperature control for wired remote controller sensor
Depending on the installed environment, correction of the wire remote temperature sensor
may be required.
Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to "Both" (01).
Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
Setting
Function number
value
35
36
(For cooling)
(For heating)
■ Setting record
 Record any changes to the settings in the following table.
Function
Setting Description
number
95
Heat Insulation condition (building insulation)
30
Room temperature control for indoor unit
sensor
31
35
Room temperature control for wired remote
controller sensor
36
After completing the Function setting, be sure to disconnect the power and reconnect it
again.

6. TEST RUN

■ Check items
(1) Is operation of each button on the remote control unit normal?
(2) Does each lamp light normally?
(3) Do air fl ow direction louvers operate normally?
(4) Is the drain normal?
(5) Do not have an abnormal noise and vibration during operation?
(6) Is there an error left in the error memory?
 After installation, check that the display is "00 (normal)".
(For checking whether the display shows "00", refer to "
Operation manual".)
- If the display is other than "00 (normal)" even though it works normally, erase the error
memory
- For "
How to check the error memory" and "
to the lower section of the "9. ERROR CODES" list.
 Do not operate the air conditioner in test run for a long time.
(If you leave it as it is after the test run starts, it will end automatically in about 60
minutes.)
En-12
Setting description
00
Standard setting
01
No correction 0 °F (0.0 °C)
02
-1 °F ( -0.5 °C)
03
-2 °F (-1.0 °C)
04
-3 °F (-1.5 °C)
05
-4 °F (-2.0 °C)
06
-5 °F (-2.5 °C)
07
-6 °F (-3.0 °C)
08
-7 °F (-3.5 °C)
09
-8 °F (-4.0 °C)
10
+1 °F (+0.5 °C)
11
+2 °F (+1.0 °C)
12
+3 °F (+1.5 °C)
13
+4 °F (+2.0 °C)
14
+5 °F (+2.5 °C)
15
+6 °F (+3.0 °C)
16
+7 °F (+3.5 °C)
17
+8 °F (+4.0 °C)
(♦... Factory setting)
Setting description
00
No correction
01
No correction 0 °F (0.0 °C)
02
-1 °F ( -0.5 °C)
03
-2 °F (-1.0 °C)
04
-3 °F (-1.5 °C)
05
-4 °F (-2.0 °C)
06
-5 °F (-2.5 °C)
07
-6 °F (-3.0 °C)
08
-7 °F (-3.5 °C)
09
-8 °F (-4.0 °C)
10
+1 °F (+0.5 °C)
11
+2 °F (+1.0 °C)
12
+3 °F (+1.5 °C)
13
+4 °F (+2.0 °C)
14
+5 °F (+2.5 °C)
15
+6 °F (+3.0 °C)
16
+7 °F (+3.5 °C)
17
+8 °F (+4.0 °C)
Cooling
Heating
Cooling
Heating
Service check in the
How to erase the error memory", refer
■ Operation method
Before starting the test run, wait for 1 minute after connecting the power supply.
By the wireless remote controller
 To start the test run, press [START/STOP(
control for 5 seconds or more by using the tip of a ballpoint pen or other small object.
By the indoor unit
 To start the test run, keep on pressing the indoor unit button for more than 10 seconds.
More
 To end test operation, press the remote controller [START/STOP(
Cooling
(When the air conditioner is running by pressing [
Less
"TIMER" Lamp will simultaneously fl ash slowly.)
Heating

7. FINISHING

(1) Insulate between pipes.
• Insulate suction and discharge pipes separately.
• For rear, right, and bottom piping, overlap the connection pipe heat insulation and
Less
indoor unit pipe heat insulation and bind them with vinyl tape so that there is no gap.
Cooling
(2) Temporarily fasten the connection cable along the connection pipe with vinyl tape.
More
(Wrap to about 1/3 the width of the tape from the bottom of the pipe so that water
Heating
does not enter.)
(3) Fasten the connection pipe to the outside wall with a saddle, etc.
(4) Fill the gap between the outside wall pipe hole and the pipe with sealer so that rain
water and wind cannot blow in.
(5) Fasten the drain hose to the outside wall, etc.
(6) Check the drainage.
Pipe
More
Connection pipe
Cooling
(heat insulation)
Less
Heating
Bind the pipes together
so that there is no gap.
Less
Cooling
More
Heating
Setting Value
GOOD
(7) Open the intake grille of the indoor unit. Set an air cleaning fi lter (accessories)
to each fi lter folder (accessories) and attach to the air fi lter. For details of how to
assemble the air fi lter, Refer to the operation manual.

8. CUSTOMER GUIDANCE

Explain the following to the customer in accordance with the operation manual:
(1) Starting and stopping method, operation switching, temperature adjustment, timer, airfl ow
switching, and other remote control unit operations.
(2) Air fi lter removal and cleaning, and how to use the air louvers.
(3) Give the operation manual to the customer.
)], press and hold [
], the "OPERATION" Lamp and
Outside wall cap*
Saddle*
(Outdoors)
Wall
Overlap the insulation
Vinyl tape*
Pipe
Wrap with cloth tape.
Cloth tape (accessory)
Drain hose
Seal A is used when the diameter of gas
pipe is Ø 1/2 in (Ø 12.70 mm) or more.
Butt connection pipe (heat
insulation) against the indoor
unit pipe (heat insulation) and
wrap with seal A so that there
is no gap.
PROHIBITED
Drain hose
Saddle
Lifted up
] on the remote
)].
Sealer putty*
*Locally purchased
Indoor unit pipe
(heat insulation)
Wave
End in water