Inverter Compressor - Fujitsu Airstage V series Service Manual

Multi air conditioning system for buildings
Hide thumbs Also See for Airstage V series:
Table of Contents

Advertisement

SERVICE PARTS INFORMATION 3

Inverter Compressor

Check Point 1 : Check Connection
p Check terminal connection of Compressor (loose or incorrect wiring)
Terminal cover opened
W
(BLACK)
Check Point 2 : Check Winding Resistance
p Check winding resistance of each terminal
If the resistance value is 0
U
W
Attention!!
If Check 1, 2 are normal, make sure the following points.
(1) Check Voltage from Filter PCB to Inverter PCB (AC380V between each terminals of LO1, LO2, LO3).
If it does not appear, check the power supply terminal.
(2) Check Voltage from Main PCB to Inverter PCB (DC16.5V between terminals of CN32 (3-4) connector
of Main PCB).
If it does not appear, replace Main PCB.
u If both of above voltages appear, it is considered to be Inverter PCB circuit failure. Replace Inverter PCB and
check operation.
U
(RED)
V
(WHITE)
or infinite, replace Compressor.
Resistance
Value (20 °C)
0.302
V
p Check connection of Inverter PCB (Loose or incorrect wiring)
INVERTER PWB
WHITE
06-90
TB-V
TB-U
TB-W
RED
compressor
AC
DC
BLACK