Check Point : ARXB07 / 09LALF

p Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.

Check Point : ARXB12 /14LALF

p Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.

Check Point : ARXB18LALF

p Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Read Wire
Resistance value(20°C)
White - Red
Red
- Black
Red
- Pink
Pink - Violet
Violet - Blue
Read Wire
Resistance value(20°C)
White - Red
Red
- Black
Red
- Pink
Pink - Violet
Violet - Blue
Read wire
Black - Yellow
White - Yellow
06-101
86.7 ± 8%
57.7 ± 8%
15.7 ± 8%
15.7 ± 8%
15.7 ± 8%
19.7 ± 8%
13.0 ± 8%
5.86 ± 8%
5.86 ± 8%
5.86 ± 8%
Resistance value (20°C)
138 ± 8%
136 ± 8%