Work Procedure After The Backup Operation; Refrigerant Shortage At The Backup Operation; Refrigerant Charging After The Compressor Replacement - Fujitsu Airstage V series Service Manual

Multi air conditioning system for buildings
Hide thumbs Also See for Airstage V series:
Table of Contents

Advertisement

6-4-3 Work procedure after the backup operation

1. Refrigerant shortage at the backup operation

When excessive refrigerant accumulates in the defective outdoor unit during the backup operation,
it becomes refrigerant shortage operation.
Method of judging refrigerant shortage from Service tool (or Web monitoring tool) is as follows.
The meaning of the sign
TH4, 5, 6, 7, 11, 12 : Outdoor unit thermistor
SV3 : Solenoid valve for liquid level detection
of the receiver tank.
EEV1 : Main EEV of the outdoor unit.
1-1. On Cooling operation
There is no liquid refrigerant in the outdoor unit receiver tank.
>>> When SV3 is ON, TH5
It often creates "Low pressure protection stop" at start up or after oil recovery operation.
>>> When LPS
Running indoor unit's EEV is fully open condition.
>>> It displays corresponding indoor unit's EEV on the chart at the bottom of the monitor.
If there is no sign of closing the EEV from fully opened condition, the refrigerant has a shortage.
1-2. On Heating operation
There is no liquid refrigerant in the outdoor unit receiver tank.
>>> When SV3 is ON, TH5
It often creates "Low pressure protection stop" at start up or after oil recovery operation.
>>> When LPS
EEV1 of outdoor unit is 500pulse. (100%).
Suction superheat is too high.
>>> When both TH4
<How to respond, when refrigerant is deficient>
Reuse the refrigerant of the broken master unit.
Connect the liquid pressure service port of the broken master unit and the low pressure service port
of the substitutional master unit by charging hose, placing the valve on the way.
>>> Refrigerant release from the receiver tank of the broken master unit.
(Refrigerant is removed until refrigerant shortage is resolved)
If refrigerant is still deficient, connect the high pressure service port of the broken master unit
and the low pressure service port of the substitutional master unit by charging hose,
and refrigerant is removed.
Not available to reuse.
>>> New refrigerant is encapsulated at substitutional master unit,
and encapsulating amount is recorded.

2. Refrigerant charging after the compressor replacement.

When the refrigerant leaks at the time of replacing the defective compressor,
charge the refrigerant as follows depending on the situation.
If the amount of recovered refrigerant is available that was pulled out of outdoor unit
which compressor was replaced.
(When the refrigerant is recovered by refrigerant recovery machine, and its weight is measured.)
>>> Perform vacuuming of repaired outdoor unit thoroughly ,
and add the refrigerant with the recovered amount.
If the amount of recovered refrigerant from outdoor unit that compressor was replaced is not sure.
>>> Once recover all units' refrigerant, and then recharge the calculated amount of
refrigerant again after vacuuming.
TH6
TH7
0.1MPa at start up, the compressor stops.
TH6
TH7
0.1MPa at start up, the compressor stops.
TH11 and TH11
06-87
TH4
TH4
TH12.
Broken
master unit
Substitutional
Slave
master unit
unit #1