Check Point : Abya30 / 36 / 45 / 54Latf; Check Point : Auxb07 / 09Latf; Check Point : Auxb12 / 14Latf - Fujitsu Airstage V series Service Manual

Multi air conditioning system for buildings
Hide thumbs Also See for Airstage V series:
Table of Contents

Advertisement

Check Point : ABYA30 / 36 / 45 / 54LATF

p Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
3
Thermal protector
120°C

Check Point : AUXB07 / 09LATF

p Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
(Black)

Check Point : AUXB12 / 14LATF

p Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
(140°C)
Pr
2
1
(AC)
(Blue)
(Violet)
(Red)
(AC)
(White)
Low(Blue)
Med(Violet)
Hi(Red)
(Black)
(AC)
(White)
Read Wire
Resistance value(20°C)
1
3
2
3
Read Wire
Resistance value(20°C)
White - Red
Blue
- Black
Red
- Violet
Violet - Blue
Read Wire
Resistance value(20°C)
White - Red
Red
- Black
Red
- Violet
Violet - Blue
06-99
22.8 ± 10%
31.9 ± 10%
658 ± 8%
329 ± 8%
99.6 ± 8%
99.6 ± 8%
455 ± 8%
541 ± 8%
103 ± 8%
103 ± 8%