Specifications
1.2

Indoor Units

Ceiling Mounted Cassette Type (Multi Flow) 600×600
Model
H1 Cooling Capacity (19.5°CWB)
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
Casing
Dimensions: (H×W×D)
Rows×Stages×Fin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output × Number
of Units
Fan
Air Flow Rate (H/L)
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Liquid Pipes
Gas Pipes
Piping
Connections
Drain Pipe
Machine Weight
H5 Sound Level (H/L) (230V)
Safety Devices
Refrigerant Control
Connectable outdoor unit
Model
Panel Color
Decoration
Dimensions: (H×W×D)
Panels
(Option)
Air Filter
Weight
Standard Accessories
Drawing No.
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m,
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m,
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m,
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
8
FXZQ20MVE
kcal/h
2,000
Btu/h
7,900
kW
2.3
kW
2.2
kcal/h
2,200
Btu/h
8,500
kW
2.5
Galvanized Steel Plate
260 (286)×575×575
mm
( ): Include Control Box
mm
2×10×1.5
0.269
QTS32C15M
Turbo Fan
W
55×1
m³/min
9/7
cfm
318/247
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Foamed Polystyrene/
Foamed Polyethylene
φ6.4 (Flare Connection)
mm
φ12.7 (Flare Connection)
mm
VP20
mm
(
External Dia. 26
Internal Dia. 20
kg
18
dBA
30/25
Fuse
Electronic Expansion Valve
R410A M Series
BYFQ60BW1
White (Ral 9010)
mm
55×700×700
Resin Net
(with Mold Resistant)
kg
2.7
Operation Manual, Installation Manual,
Paper Pattern for Installation, Drain
Hose, Clamp Metal, Washer Fixing
Plate, Sealing Pads, Clamps, Screws,
Washer for Hanging Bracket,
Insulation for Fitting.
level difference: 0m.
level difference: 0m.
level difference; 0m. (Heat pump only)
these values are normally somewhat higher as a result of installation conditions.
FXZQ25MVE
2,500
9,900
2.9
2.8
2,800
10,900
3.2
Galvanized Steel Plate
260 (286)×575×575
( ): Include Control Box
2×10×1.5
0.269
QTS32C15M
Turbo Fan
55×1
9/7
318/247
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Foamed Polystyrene/
Foamed Polyethylene
φ6.4 (Flare Connection)
φ12.7 (Flare Connection)
VP20
)
(
External Dia. 26
Internal Dia. 20
18
30/25
Fuse
Electronic Expansion Valve
R410A M Series
BYFQ60BW1
White (Ral 9010)
55×700×700
Resin Net
(with Mold Resistant)
2.7
Operation Manual, Installation Manual,
Paper Pattern for Installation, Drain
Hose, Clamp Metal, Washer Fixing
Plate, Sealing Pads, Clamps, Screws,
Washer for Hanging Bracket,
Insulation for Fitting.
3D038929A
SiBE39-402A
FXZQ32MVE
3,150
12,500
3.7
3.6
3,400
13,600
4.0
Galvanized Steel Plate
260 (286)×575×575
( ): Include Control Box
2×10×1.5
0.269
QTS32C15M
Turbo Fan
55×1
9.5/7.5
335/265
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Foamed Polystyrene/
Foamed Polyethylene
φ6.4 (Flare Connection)
φ12.7 (Flare Connection)
VP20
)
(
External Dia. 26
Internal Dia. 20
18
32/26
Fuse
Electronic Expansion Valve
R410A M Series
BYFQ60BW1
White (Ral 9010)
55×700×700
Resin Net
(with Mold Resistant)
2.7
Operation Manual, Installation Manual,
Paper Pattern for Installation, Drain
Hose, Clamp Metal, Washer Fixing
Plate, Sealing Pads, Clamps, Screws,
Washer for Hanging Bracket,
Insulation for Fitting.
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications
)