Transmission Error Between Indoor Units And Outdoor Units, Open Phase In Power Supply Wiring - Daikin VRV EMERION RXYQ-AATJA Service Manual

Hide thumbs Also See for VRV EMERION RXYQ-AATJA:
Table of Contents

Advertisement

Troubleshooting by Error Code
3.62 Transmission Error between Indoor Units and Outdoor
Units, Open Phase in Power Supply Wiring
Applicable
All indoor unit models
Models
All outdoor unit models
U4
Error Code
Method of Error
Microcomputer checks if transmission between indoor and outdoor units is normal.
Detection
Error Decision
Transmission is not carried out normally for a certain amount of time.
Conditions
Supposed
 Open phase in power supply wiring
Causes
 Short circuit in indoor-outdoor or outdoor-outdoor transmission wiring (F1/F2), or wrong wiring
 Outdoor unit power supply is OFF
 System address does not match
 Defective indoor unit control PCB
 Defective outdoor unit main PCB
 Multi-tenant function is ON.
345
SiUS342303E
Part 6 Service Diagnosis

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrv emerion rxyq-aayda

Table of Contents