List Of Electrical And Functional Parts; Outdoor Unit - Daikin R-410A Service Manual

Vrv ii-sr-410a heat pump 50hz
Hide thumbs Also See for R-410A:
Table of Contents

Advertisement

List of Electrical and Functional Parts

1. List of Electrical and Functional Parts
1.1

Outdoor Unit

Item
Inverter
Compressor
Crankcase heater (INV)
Motor
Fan motor
Over-current relay
Electronic expansion
valve (Main)
Electronic expansion
valve (Subcool)
Functional
parts
Solenoid valve (Hot gas)
Solenoid valve (Receiver gas
charge)
4 way valve
Pressure switch (INV)
Pressure-
Fusible plug
related parts
Pressure sensor (HP)
Pressure sensor (LP)
For outdoor air
For suction pipe
Main
For discharge pipe
Thermistor
PCB
For heat exchanger
For subcooling heat
exchanger
Others
Fuse (A3P)
28
Name
Symbol
Type
M1C
Output
E1HC
M1F·M2F
Cooling
Y1E
Heating
Cooling
Y2E
Heating
Y1S
Y2S
Y3S
S1PH
S1NPH
S1NPL
R1T
R2T
R3T
R4T
R5T
F1U
Model
4HP
5HP
JT100FCVD@4
3.2kW
33W
0.07kW
3.2A
1400pls
PI control
PI control
0pls
TEV1620DQ2
TEV1620DQ2
VT40100
ACB-4UB11
ON: 3.8+0/-0.1MPa OFF: 2.85±0.15MPa
FPGH-3D 70~75°C
PS8051A 0~4.15MPa
PS8051A –0.05~1.7MPa
3.5~360kΩ
3.5~360kΩ
3.5~400kΩ
3.5~360kΩ
3.5~360kΩ
AC250V 6.3A Time lag fuse
List of Electrical and Functional Parts
SiBE39-402A
Remark
(PCB terminal)
6HP
A1P X6A
A1P X26A
A1P X28A
A1P X2A
A1P X3A
A1P X5A
A2P X60A
A1P X46A
A1P X45A
A1P X44A
A1P X37A 1-2Pin
A1P X34A 1-2Pin
A1P X37A 3-4Pin
A1P X37A 5-6Pin

Hide quick links:

Advertisement

Table of Contents
loading