Daikin R-410A Service Manual page 103

Vrv ii-sr-410a heat pump 50hz
Hide thumbs Also See for R-410A:
Table of Contents

Advertisement

SiBE39-402A
Detailed Setting Procedure of Low Noise Operation and Demand Control
1. Setting mode 1 (H1P off)
$ In setting mode 2, push the BS1 (MODE button) one time. → Setting mode 2 is entered and
2. Setting mode 2 (H1P on)
$ In setting 1, push and hold the BS1 (MODE button) for more than 5 seconds. → Setting
% Push the BS2 (SET button) several times and match the LED display with the Setting No.
& Push the BS3 (RETURN button) one time, and the present setting content is displayed.
' Push the BS3 (RETURN button) two times. → Returns to $.
( Push the BS1 (MODE button) one time. → Returns to the setting mode 1 and turns H1P off.
Test Operation
H1P lights.
During the setting mode 1 is displayed, "In low noise operation" and "In demand control" are
displayed.
mode 2 is entered and H1P lights.
you want.
→ Push the BS2 (SET button) several times and match the LED display with the setting
content (as shown below) you want.
Field Setting
93