Field Setting
Image of operation in the case of A
Operation sound
Rated operation
sound
Operation sound of
Low noise of approx. 2 to 3 dB
mode 1
(The power consumption may
be decreased by about 10%)
Operation sound of
Low noise of approx. 3 to 5 dB
mode 2
(The power consumption may
be decreased by about 20%)
Operation sound of
Low noise of approx. 5 to 8 dB
mode 3
(The power consumption may
be decreased by about 30%)
Image of operation in the case of B
Operation sound
Time set with "Night-time low noise start setting"
Rated operation
sound
Operation sound
of mode 1
Operation sound
of mode 2
Operation sound
of mode 3
Image of operation in the case of A, B
Operation sound
Time set with "Night-time low noise start setting"
Rated operation
sound
Operation sound
of mode 1
Operation sound
of mode 2
Operation sound
Low noise mode instructing
of mode 3
Operation sound set with
"External low noise setting"
90
If capacity precedence is set in "Capacity
precedence setting", the fan speed will be
increased according to the load of air
conditioning when load is heavier.
PM 8:00
PM 10:00
PM 0:00
Set with "Night-time low noise start setting".
(Factory setting is "PM 10:00"
If capacity precedence is set in "Capacity
precedence setting", the fan speed will be
increased according to the load of air
conditioning when load is heavier.
* Operation sound
level set with
"Night-time low
noise setting"
PM 8:00
PM 10:00
PM 0:00
Set with "Night-time low noise start setting".
(Factory setting is "PM 10:00"
If capacity precedence is set in
"Capacity precedence setting",
the fan speed will be increased
according to the load of air
conditioning when load is heavier.
Low noise mode instructing
Operation sound level set with "External low noise setting"
Night time
Operation sound level set with
"Night-time low noise setting"
AM 6:00
Set with "Night-time low noise start setting".
(Factory setting is "AM 8:00"
Time set with " Night-time low noise end setting"
* Night time
* Low noise mode
instructing
* Operation sound set with
"External low noise setting"
AM 6:00
Set with "Night-time low noise start setting".
(Factory setting is "AM 8:00"
Operation sound during low
noise mode is instructed can
be set with "External low
noise level setting"
(Factory setting is "Mode 2".)
Time set with "Night-time low noise end setting"
Operation sound during
night-time low noise mode is
instructed can be set with
"Night-time low noise level
setting"
(Factory setting is "OFF".)
AM 7:00
AM 8:00
Operation sound during low noise
mode is instructed can be set with
"External low noise level setting"
(Factory setting is "Mode 2".)
Operation sound during night-time
low noise mode is instructed can
be set with "Nigh-time low noise
level setting"
(Factory setting is "OFF".)
When external low noise
instruction is received during
the operation with night-time
low noise mode.
AM 7:00
AM 8:00
Mode 2 precedes Mode 1 and
Mode 3 precedes Mode 2.
SiBE39-402A