Daikin R-410A Service Manual page 17

Vrv ii-sr-410a heat pump 50hz
Hide thumbs Also See for R-410A:
Table of Contents

Advertisement

SiBE39-402A
Model Name
H1 Cooling Capacity
H2 Heating Capacity
Casing Color
Dimensions: (H×W×D)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor Output×Number
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
Drive
Liquid Pipe
Connecting
Pipes
Gas Pipe
Machine Weight
Safety Devices
Defrost Method
Capacity Control
Refrigerant Name
Refrigerant
Charge
Control
Refrigerator
Oil
Charge Volume
Standard Accessories
Drawing No.
Notes:
H1 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m,
H2 Indoor temp. : 20°CDB / outdoor temp. : 7°CDB or 6°CWB / Equivalent piping length : 7.5m,
Specifications
RXYSQ6M7V3B
kcal / h
Btu / h
kW
kcal / h
Btu / h
kW
mm
1,345×900×320
Hermetically Sealed Scroll Type
m³/h
r.p.m
kW
W
m³/min
φ9.5 (Flare Connection)
mm
φ19.1 (Brazing Connection)
mm
kg
High Pressure Switch, Fan Driver Overload Protector, Inverter
Overload Protector, Fusible Plugs, Fuse
Reverse cycle defrosting
%
kg
Electronic Expansion Valve
DAPHNE FVC68D
L
Installation Manual, Operation Manual, Clamps, Auxiliary Piping
level difference : 0m.
level difference : 0m.
13,300
52,900
15.5
15,400
61,400
18.0
Ivory White
Cross Fin Coil
19.36
6,480
3.5×1
Direct on line
Propeller Fan
70×2
106
Direct Drive
127
24~100
R410A
5.8
1.6
4D045796
Specifications
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3