Display "Under Host Computer Integrate Control" Blinks (Repeats Double Blink) - Daikin R-410A Service Manual

Vrv ii-sr-410a heat pump 50hz
Hide thumbs Also See for R-410A:
Table of Contents

Advertisement

SiBE39-402A
6.3
Display "Under Host Computer Integrate Control" Blinks
(Repeats Double Blink)
Remote
"under host computer integrated control" (Repeats double blink)
Controller
Display
Applicable
Unified ON/OFF controller
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
! Central control address (group No.) is not set for indoor unit.
Supposed
! Improper address setting
Causes
! Improper wiring of transmission wiring
Troubleshooting
Troubleshooting
Troubleshooting by Indication on the Unified ON/OFF Controller
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Is the central
NO
control address (group
No.) set for the
indoor unit?
YES
Is the switch
NO
for setting each address
set correctly?
YES
Is the
transmission
YES
wiring disconnected or
wired incorrectly?
NO
Set by remote controller the
central control address for all
indoor units connected to the
central control line.
Set the switch for setting each
address correctly and
simultaneously reset the power
supply for all optional controllers
for centralized control.
Fix the wiring correctly.
Replace the PC board of the
unified ON/OFF controller.
(V2844)
177