SiBE39-402A

3.1.3 Simplified Remote Controller

BRC2A51
! Group No. setting by simplified remote controller.
1. Remove the cover of remote controller.
2. While in normal mode, press the [BS6] BUTTON (field set) to enter the FIELD SET MODE.
3. Select the mode No. [00] with [BS2] BUTTON (temperature setting s) and [BS3] BUTTON
4. Select the group No. with [BS9] BUTTON (set A) and [BS10] BUTTON (set B). (Group Nos.
5. Press [BS7] BUTTON (set/cancel) to set group No.
6. Press [BS6] BUTTON (field set) to return to the NORMAL MODE.
Test Operation
Mode No.
Unit No.
(temperature setting t).
increase in the order of 1-00, 1-01......1-15, 2-00,.....4-15. However, the unified ON/OFF controller
displays only group No. set within the range of control.)
First
Code No.
Second
Code No.
Field Setting
71