Daikin R-410A Service Manual page 186

Vrv ii-sr-410a heat pump 50hz
Hide thumbs Also See for R-410A:
Table of Contents

Advertisement

Troubleshooting by Indication on the Unified ON/OFF Controller
176
2A
Is the
wiring adaptor for
electrical appendices
connected?
NO
Is a schedule timer
connected?
NO
Are
there two or
more optional
controllers for centralized
control connected with the
connector for setting
master
control?
NO
Reset the power supply for
all optional controllers for
centralized control
simultaneously.
If the malfunction is still not cleared:
YES
YES
Is a data station
connected?
NO
Is a parallel interface
connected?
NO
Is the
schedule timer's
individual/combined
connector
connected?
NO
YES
SiBE39-402A
Cannot be used in
combination with a wiring
adaptor for electrical
appendices. Remove the
wiring adaptor for electrical
appendices and reset the
power supply for all optional
controllers for centralized
control simultaneously.
YES
Schedule timer and data
station cannot be used in
combination. Disconnect
either the schedule timer or
data station and reset the
power supply for all optional
controllers for centralized
control simultaneously.
YES
Schedule timer and parallel
interface cannot be used in
combination. Disconnect
either the schedule timer or
parallel interface and reset the
power supply for all optional
controllers for centralized
control simultaneously.
YES
Disconnect the schedule
timer's individual / combined
connector and reset the power
supply for all optional
controllers for centralized
control simultaneously.
Arrange so that the connector
for setting master control is
connected to one controller for
centralized control and reset
the power supply for all
optional controllers for
centralized control
simultaneously.
Disconnect the connector for
setting master control from
the master controller, connect
to another optional controller
for centralized control and
simultaneously reset all
optional controllers for
centralized control again. The
controller connected by the
connector for setting master
control when the malfunction
is cleared is defective and
must be replaced.
Troubleshooting
(V2843)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents