Field Setting; Field Setting From Remote Controller - Daikin R-410A Service Manual

Vrv ii-sr-410a heat pump 50hz
Hide thumbs Also See for R-410A:
Table of Contents

Advertisement

SiBE39-402A

3. Field Setting

3.1

Field Setting from Remote Controller

Individual function of indoor unit can be changed from the remote controller. At the time of
installation or after service inspection / repair, make the local setting in accordance with the
following description.
Wrong setting may cause malfunction.
(When optional accessory is mounted on the indoor unit, setting for the indoor unit may be
required to change. Refer to information in the option handbook.)
3.1.1 Wired Remote Controller <BRC1A61, 62>
1. When in the normal mode, push the
2. Select the desired "mode No." with the
3. During group control and you want to set by each individual indoor unit (when mode No. 20,
4. Push the
5. Push the
6. Push the timer
7. Push the
(Example)
When setting the filter sign time to "Filter Dirtiness-High" in all group unit setting, set the Mode
No. to "10", Mode setting No. to "0" and setting position No. to "02".
Test Operation
Unit No.
Second Code No.
First Code No.
enters the "field set mode."
21, 22, 23, 25 has been selected), push the time mode
unit No." to be set.
Note: This operation is not required when setting as a group.
button and select the first code No.
button and select the second code No.
button one time and "define" the currently set contents.
button to return to the normal mode.
Mode No.
Field Set Mode
button for 4 seconds or more, and operation then
button.
button and select the "indoor

Field Setting

69