Command – 03
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
The arrangement of the terminal assignment data permits you to assign all inputs in a single
command. The example below shows a transmission to the inverter at address Node 1 to set the
Forward command, Multi-speed 1 and Multi-speed 2.
Sum the three data strings:
(STX) | 01 | 02 | 0x000000000000000D | (BCC) | (CR)
02 | 30 31 | 30 31 | 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 68 | 30 35 | 0D
The 03 command reads the monitor data as a single block.
The frame format of command 03 follows the
diagram and specification table. The transmit
frame has no data field.
Element
Description
STX
Control code (STart of TeXt)
Node
Node (station) address of inverter
Command
Transmission command
BCC
Block check sum code
[CR]
Control code (carriage return)
The receive frame has a 104-byte data field,
containing values for 13 items.
Element
Description
STX
Control code (STart of TeXt)
Node
Node (station) address of inverter
Data
Transmission data
BCC
Block check sum code
[CR]
Control code (carriage return)
0x0000000000000001
+ 0x0000000000000004
+ 0x0000000000000008
= 0x000000000000000D
to ASCII
Transmit frame format
STX Node
Size
1 byte
STX (0x02)
2 bytes 01 to 32
2 bytes 03
2 bytes Exclusive OR of Node,
Command, and Data
1 byte
[CR] (0x0D)
Receive frame format
STX Node
Size
1 byte
STX (0x02)
2 bytes 01 to 32
104
(see next table)
bytes
2 bytes Exclusive OR of Node,
Command, and Data
1 byte
[CR] (0x0D)
B–9
SJ700
Inverter
2
Command
BCC [CR]
Value
Data
BCC [CR]
Value