Several parameter settings are necessary to configure serial communications, listed below.
Function
Item
Code
C071
Baud rate
C072
Node address
C073
Data bits
C074
Parity
C075
Stop bits
C078
Wait time
C079
Communication
protocol select
For inverters on the same network, some settings must match from inverter to inverter. These
include: Baud rate, data bits, parity, and stop bits. However, the node address on each inverter
must be unique, used only once on the network.
Use the communication test mode to check the RS485 serial port hardware on the inverter. Use
the following procedure:
1. Disconnect the wiring from the TM2 serial port terminal block on the inverter.
2. Set parameter C071 = 02 (loopback test)
3. Turn the inverter power OFF and then ON again to initiate the communication test.
4. Check the pass/fail results according to the keypad display.
Normal termination
5. Press the STOP/RESET key on the digital operator keypad (or the Reset button on the copy
unit) to switch to the normal setting display.
6. Set parameter C071 to the desired setting for normal operation.
Value
Description
02
Loop-back test
03
2400 bps
04
4800 bps
05
9600 bps
06
19200 bps
1 to 32,
1 to 32 – Node or station address (unique
FF
to each inverter or device)
FF – Automatic broadcast (to all nodes on
transmit, allowed only on certain
commands (refer to each command
description in this appendix)
07
7 bits
08
8 bits
00
none
01
Even parity
02
Odd parity
01
1 bit
02
2 bits
0 to 1000 0 to 1000 ms time that the inverter waits
to respond to network master
00
ASCII
01
ModBus RTU