Hitachi SJ7002 Series Instruction Manual page 261

Sj7002 series
Hide thumbs Also See for SJ7002 Series:
Table of Contents

Advertisement

6–14
Monitoring Trip Events, History, & Conditions
Easy Sequence
Error Codes
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Use the following table to diagnose errors related to Easy Sequence programming. The error
code will appear when the related program runs.
Error Code: OPE / SRW
E43.-
PRG.CMD
E44.-
PRG.NST
E45.-
PRG.ERR1
E50.- ... E59.-
PRG-0 ... PRG-9
DeviceNet Expansion Card Errors
Name
Invalid instruction
A program contains an invalid instruction
The [PRG] terminal was turn ON but a
program was not loaded
Nesting count error
Subroutines with FOR and NEXT
instructions are nested more than eight
levels
Execution error 1
A FOR (or another) instruction to begin
nesting is not found at the jump destina-
tion of a GO TO instruction, and the
NEXT (or another) instruction to end
nesting precedes the beginning of nesting
An arithmetic operation resulted in overflow
or underflow, or a divide-by-zero was
attempted
A CHG PARAM or MON PARAM instruc-
tion attempts to:
• Reference an undefined parameter
• Set a value outside the range for a parameter
• Update a parameter that cannot be changed
during inverter operation
User trip event
A TRIP instruction was executed in a
program
Probable Cause(s)