The SJ700
inverter features auto-tuning, which detects and records the motor characteristic
2
parameters to use in all vector control modes. Auto-tuning determines the resistance and
inductance of motor windings. Therefore, the motor must be connected to the inverter for this
procedure. Note that the auto-tuning feature is not associated with PID loop operation, which is
common on some control devices. The auto-tuning procedure must be conducted while the
inverter is stopped (not in Run mode), so it can use special output pulses to detect motor
characteristics.
When using the inverter in sensorless vector control, sensorless vector control - 0Hz domain, or
vector control with encoder feedback, the motor circuit constants are important. If they are
unknown, then you must first conduct the auto-tuning procedure. The inverter will determine
the constants and write new values for the related "H" Group settings. The auto-tuning proce-
dure requires that the inverter be configured to operate the 1st motor (do not set the inverter to
use 2nd and 3rd motor data during an auto-tuning procedure).
Func.
Name
Auto-tuning setting
H001
Motor data selection, 1st motor
H002
Motor capacity, 1st motor
H003
H004
Motor poles setting, 1st motor
Auto-tuned motor constant R1,
H030
1st motor
Auto-tuned motor constant R2,
H031
1st motor
Auto-tuned motor constant L,
H032
1st motor
Auto-tuned motor constant Io,
H033
1st motor
Auto-tuned motor constant J, 1st
H034
motor
A003
Base frequency setting
DC braking enable
A051
AVR voltage select
A082
Please read the following Warning before running the auto-tuning procedure on the next page.
WARNING: You may need to disconnect the load from the motor before performing auto-
tuning. The inverter runs the motor forward and backward for several seconds without regard to
load movement limits.
SJ700
Range
00
Disabled
01
Enabled, without motor rotation
02
Enabled, with motor rotation
00
Standard motor parameters
01
Auto-tuning parameters
02
Adaptive tuning parameters
0.2 – 75,
kW, up to –550xxx models
0.2 – 160
kW, –750xxx to –1500xxx
models
2 / 4 / 6 / 8
Units: poles
Units: ohms
Units: ohms
Units: mH
Units: A
Units: kgm
30 to maximum freq.
Units: Hz
00
Disabled (Disable during auto-
tuning)
01
Enabled
200/215/220/230/240 Valid for 200V class inverters
380/400/415/440/
Valid for 400V class inverters
460/480
4–71
Inverter
2
Notes
2