Hitachi SJ7002 Series Instruction Manual page 195

Sj7002 series
Hide thumbs Also See for SJ7002 Series:
Table of Contents

Advertisement

4–34
Using Intelligent Input Terminals
Expansion Card
Input Signals
45=[ORT]
Opt. Code
46=[LAC]
and
47=[PCLR]
Symbol
48=[STAT]
Valid for
[1] to [8]
Inputs
B120=01;
Required
Set B121 to
Settings
B126
...on SJ-FB
Wiring
Expansion
terminals
Card
ADD Frequency
Enable
50
Opt. Code
[ADD]
Symbol
Valid for
[1] to [8]
Inputs
Required
A145, A146
Settings
Default
Requires
terminal
config.
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Other inputs listed below require the expansion card SJ-FB Encoder Feedback. Please see the
SJ-FB manual for more information.
Symbol
Function Name
ORT
Orientation
LAC
LAD Cancel
PCLR
Position deviation clear
STAT
Pulse train input enable
The diagram below shows how the Input/Output connections for the SJ–FB feedback board.
The inverter's internal connections and parameter configuration make these signals available on
intelligent input and output terminals.
ORT
LAC
PCLR
STAT
Input assignments
The information on outputs related to the SJ-FB expansion card is in
Signals" on page 4–54
.
The inverter can add or subtract an offset value to the output frequency setting which is speci-
fied by A001 (will work with any of the five possible sources). The ADD Frequency is a value
you can store in parameter A145. The ADD Frequency is summed with or subtracted from the
output frequency setting only when the [ADD] terminal is ON. Function A146 selects whether
to add or subtract. By configuring an intelligent input as the [ADD] terminal, your application
can selectively apply the fixed value in A145 to offset (positively or negatively) the inverter
output frequency in real time.
Keypad potentiometer
Control terminal
Function F001 setting
Network variable F001
Calculate function output
A145 Add frequency
Intelligent input
Orientation (home search sequence)
Cancels the linear acceleration/deceleration position
control in the feedback card
Forces the position error to zero
Starts the pulse train control of motor frequency
SJ700
inverter
2
SJ-FB Feedback
Expansion Card
Output assignments
Input
Output
terminals
terminals
Control and logic connector
A001 Frequency source setting
Output frequency setting
Σ
+/–
[ADD]
Description
ZS
DSE
POK
"Expansion Card Output
A146
ADD direction select

Advertisement