Suppose the electronic thermal setting (B012) is set to 44 Amperes. The left graph below shows
the effect of the free setting torque characteristic curve. For example, at (B017) Hz, the output
current level to cause overheating in a fixed time period is reduced by a factor of (B018). The
right graph below shows the reduced trip current levels in those conditions for given trip times.
Trip
time (s)
60
0.5
0
Reduced trip current at (B017) Hz
Any intelligent output terminal may be programmed to indicate a thermal warning [THM].
Parameter C061 determines the warning threshold. Please see
page 4–52
for more details.
Name/
Description
Level of electronic thermal setting
Level of electronic thermal setting, 2nd motor
Level of electronic thermal setting, 3rd motor
Electronic thermal characteristic
Electronic thermal characteristic,
2nd motor
Electronic thermal characteristic,
3rd motor
Free setting, electronic thermal frequency (1)
Free setting, electronic thermal current (1)
Free setting, electronic thermal frequency (2)
Free setting, electronic thermal current (2)
Free setting, electronic thermal frequency (3)
Free setting, electronic thermal current (3)
A
(x)
(y)
(z)
Keypad
Range and Settings
SRW
OPE
0.20 x rated current) to
(2.00 x rated current) (A)
0.20 x rated current) to
(2.00 x rated current) (A)
0.20 x rated current) to
(2.00 x rated current) (A)
00
SUB
Reduced torque
0 1
CRT
Constant torque
02
FREE
V/f free-setting
00
SUB
Reduced torque
0 1
CRT
Constant torque
02
FREE
V/f free-setting
00
SUB
Reduced torque
0 1
CRT
Constant torque
02
FREE
V/f free-setting
0.0 to 400.0 (Hz);
model -4000HFx2 is
0.00 to 120.0 (Hz)
0.0 to 1000. (A)
0.0 to 400.0 (Hz);
model -4000HFx2 is
0.00 to 120.0 (Hz)
0.0 to 1000. (A)
0.0 to 400.0 (Hz);
model -4000HFx2 is
0.00 to 120.0 (Hz)
0.0 to 1000. (A)
SJ700
Inverter
2
(x) = B018 value x 116%
(y) = B018 value x 120%
(z) = B018 value x 150%
"Thermal Warning Signal" on
Defaults
FEF2
FUF2
FF2
FE2
FU2
F2
(EU)
(USA)
(Jpn)
rated current of inverter
rated current of inverter
rated current of inverter
01
01
00
01
01
00
01
01
00
0.
0.
0.
0.0
0.0
0.0
0.
0.
0.
0.0
0.0
0.0
0.
0.
0.
0.0
0.0
0.0
3–35
Run
Mode
Edit
Lo Hi
✘ ✔
✘ ✔
✘ ✔
✘ ✔
✘ ✔
✘ ✔
✘ ✔
✘ ✔
✘ ✔
✘ ✔
✘ ✔
✘ ✔