Monitoring Trip Events, History, & Conditions; Error Codes - Hitachi SJ7002 Series Instruction Manual

Sj7002 series
Hide thumbs Also See for SJ7002 Series:
Table of Contents

Advertisement

6–6
Monitoring Trip Events, History, & Conditions

Error Codes

OPE / SRW
Display
E0 1.-
OC.Drive
E02.-
OC.Decel
E03.-
OC.Accel
E04.-
Over.C
E05.-
OL.BRD
E06.-
OL.BRD
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
An error code will appear on the display automatically when a fault causes the inverter to trip.
The following table lists the cause associated with the error.
Name
Over-current
If the motor is constrained
protection
or suddenly accelerated or
decelerated, a high current
will flow in the inverter
and the inverter may fail.
To avoid this problem, the
inverter shuts off its output
Over-current
and displays the error code
protection
shown on the left when it
detects a current higher
than a specified level. This
Over-current
protective function uses a
protection
DC current detector (CT)
to detect over-current.
When a current as high as
about 220% of the
inverter's rated output
current is detected, the
protective circuit operates
and the inverter trips.
Over-current
protection
Overload
This protective function monitors the
protection
inverter output current, and shuts off the
(*1) (*4)
inverter output and displays the error code
shown on the left when the internal
electronic thermal protection circuit
detects a motor overload. If the error
occurs, the inverter will trip according to
the setting of the electronic thermal
function.
Braking
When the BRD operation rate exceeds the
resistor
setting of B090, this protective function
overload
shuts off the inverter output and displays
protection
the error code shown on the left.
Description
During
constant
speed
operation
During
deceleration
During
acceleration
Other
conditions
Note: The electronic thermal protection is
easily triggered when the output frequency is
5 Hz or less. If the moment of inertia of the
load is large, this protective function may
operate when the inverter accelerates the
motor and the acceleration may be disabled.
If this problem occurs, increase the torque
boost current or adjust other settings as
needed.
Note: Confirm the maximum allowable
capacity of the resistor.
Troubleshooting and
Corrective Action
Check whether the load has fluctuated
sharply.
Check for the short circuit of output
connections (check the output cables).
Check for a ground fault (check the
output cables and motor).
Check whether the inverter has deceler-
ated the motor quickly increase the decel-
eration time).
Check whether the inverter has acceler-
ated the motor quickly (increase the
acceleration time).
Check whether the motor has been locked
(check the motor and wiring).
Check whether the torque boost current
has been set too high (reduce the boost
current).
Check whether the DC braking force is
too high (reduce the braking force).
Check whether the current detector (CT)
is normal (replace or repair the CT).
Check whether the motor load is too high.
(reduce the load factor).
Check whether the thermal level is appro-
priate (adjust the level appropriately).
Check whether the inverter has decreased
the motor quickly (increase the decelera-
tion time).
Check whether the operation cycle is too
short (prolong the operation cycle)
Check whether the set BRD operation
rate is too low (adjust the setting to an
appropriate level).