Hitachi SJ7002 Series Instruction Manual page 136

Sj7002 series
Hide thumbs Also See for SJ7002 Series:
Table of Contents

Advertisement

Option
Code
29
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
50
51
52
53
54
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Terminal
Function Name
Symbol
UDC
Remote Control Data
Clearing
OPE
Operator Control
SF1
Multi-speed bit 1
SF2
Multi-speed bit 2
SF3
Multi-speed bit 3
SF4
Multi-speed bit 4
SF5
Multi-speed bit 5
SF6
Multi-speed bit 6
SF7
Multi-speed bit 7
OLR
Overload restriction
TL
Torque limit enable
TRQ1
Torque limit selection, bit
1
TRQ2
Torque limit selection, bit
2
PPI
Proportional /
Proportional/Integral
mode selection
BOK
Brake confirmation signal Indicates external brake has released (used only for external
ORT
Orientation (home search) The encoder is in the home (oriented) position
LAC
LAC: LAD cancel
PCLR
Position deviation reset
STAT
Pulse train position
command input enable
ADD
Add frequency enable
F-TM
Force terminal mode
ATR
Torque control enable
KHC
Clear cumulative power
value
SON
Speed servo ON
Input Function Summary Table
Clears the UP/DWN frequency memory by forcing it to equal
the set frequency parameter F001. Setting C101 must be
set=00 to enable this function to work.
Forces the source of the output frequency setting (A001) and
the RUN command (A002) to be from the digital operator
(F001 and the Run key, respectively)
Multiple speed select, Bit 1
Multiple speed select, Bit 2
Multiple speed select, Bit 3
Multiple speed select, Bit 4
Multiple speed select, Bit 5
Multiple speed select, Bit 6
Multiple speed select, Bit 7
Turn ON to select current overload parameter set 2
(B024, B025, B026); OFF selects set 1(B021, B022, B023)
ON enables torque limit feature; OFF disables all torque limit
sources and defaults to 200% of inverter rated torque output
Binary encoded torque limit select, Bit 1 (LSB)
Binary encoded torque limit select, Bit 2 (MSB)
ON selects Proportional-only control; OFF selects Propor-
tional-Integral control
brake control function)
Disables the normal Linear Accel / Decel (LAD) mode
Clears the position deviation by setting the actual position
equal to the desired position
Enables the pulse train control of motor
Adds the A145 value (Add Frequency) to the output
frequency
Force inverter to use input terminals for output frequency and
Run command sources
Inverter operates by controlling torque instead of speed
Clears cumulative power data displayed by parameter D015
Enables the inverter to accept FW/REV commands; for use
with V/F curve vector control with sensor (A044=05)
SJ700
Inverter
2
Description
3–53