Trip History and
Inverter Status
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
We recommend that you first find the cause of the fault before attempting clearing it. When a
fault occurs, the inverter stores important performance data at the moment of the fault. To
access the data, use the monitor functions (Dxxx) and select D081 for details about the present
fault (E
). The previous five faults are stored in D081 to D086, with D (E
n
shifts D081–D085 to D082–D086, and writes the new error to D081.
The following Monitor Menu map shows how to access the error codes. When fault(s) exist,
you can review their details by first selecting the proper function: D081 is most recent, and
D086 is the oldest.
2
d08 1
Error
exists?
E07.2
60.00
4.00
270.0
15
18
Monitor Menu
2
2
d086
1
FUNC.
No error
No
Yes
Current Trip
Conditions
Error Code
1
Output frequency at
trip point
1
Motor current at
trip point
1
DC bus voltage at
trip point
1
Cumulative inverter
operation time
at trip point
1
Cumulative power-
ON time at trip point
1
FUNC.
SJ700
Inverter
2
to E
). Each error
n-1
n-5
Trip History
2
1
d082
FUNC.
6–15