Specifications

Suppression Release Peripheral 4090-9005 and 4090-9006
Communications
RAC Output Rating, with 4010 control panel*
NAC Power Requirements
NOTE: 4010 NACs are
rated 2 A; 4009 IDNet
NAC Extender standard
NACs are rated at 2 A,
Extender expansion NACs
are rated 1.5 A
Wire Connections
IDNet Wiring Distance Reference
Dimensions
Operating Temperature
Operating Humidity Range
Coil Supervision Module 2081-9046
Construction
Dimensions
Wiring
Current Rating
* Refer to data sheet S4100-0040 for application information when using the Suppression Release Peripheral with the 4100U Series Fire
Alarm Control Panels.

Compatible UL Listed Valves and Actuators

MFG.
Model Number
*AUTOMAN II-C Assembly; solenoid 17728;
coil 25924
AUTOMAN II-C Explosion-Proof Releasing
Device; solenoid 31492; coil 31438
*AUTOMAN II-C Assembly; solenoid 68739;
coil 25924,
A
Solenoid Electric Actuator; solenoid 73111;
N
coil 73097
S
U
*CV90 HF Electric Actuator 73327; may use
L
73606 in-line resistor for 12 VDC
LP CO2 w/ASCO solenoid 422934,
LP CO2 double action solenoid 430948
LP CO2 3-way selector valve solenoid
433419
Electric Actuator 24 VDC solenoid 570537
Solenoid 26114002 for Solenoid Coupling
Assemblies: 21006401 & 21006402; &
LPG
LPG128/145/190/230-50/55 FM-200 valves;
and LPG128-90UL iFLOW & FM-200 valves
S
71395SN2ENJ1NOH111C2 (Skinner coil H111C2) 1/4", NPS, 1/16"
k
73212BN4TN00NOC111C2 (Skinner coil C111C2) 1/2", 5-300 psi
i
n
73212BN4TNLVNOC322C2 (Skinner coil C322C2) 1/2", NPS, 0.92 A, 250 psi
n
73218BN4UNLVNOH111C2 (Skinner coil H111C2)
e
73218BN4UNLVNOC111C2 (Skinner coil C111C2) 1/2", NPS, 5/8 in. orifice
r
* 12 VDC coils, either wire two in series for 24 VDC activation, or, if available from manufacturer, use series resistor
IDNet, one address
1 A maximum @ nominal 24 VDC, regulated
Voltage 16 to 32 VDC (nominal 24 VDC)
No additional current required, circuit appears as standard end-of-line (EOL)
Supervisory Current
NAC loading
Alarm Current
Reference
(RAC current =
actuator current)
Screw terminals for input and output wiring, 18 to 12 AWG wire
(0.82 mm
Up to 2500 ft (762 m) from the IDNet communications source module
Up to 10,000 ft (3048 m) total Class B wiring distance including T-Taps
Compatible with Simplex 2081-9044 Overvoltage Protectors
See installation reference on page 8
32° to 120° F (0° to 49° C) indoor operation only
10 to 90% RH at 90° F (32° C)
Epoxy encapsulated
1-3/8" W x 2-7/16" L x 1-1/16" H (34 mm x 62 mm x 27 mm)
18 AWG (0.82 mm
2 A maximum; internally fused at 3 A, non-replaceable
Coil Details
12 VDC, 458 mA
24 VDC, 467 mA
12 VDC, 458 mA
24 VDC, 1 A
9 VDC max,
450 mA
24 VDC, 442 mA
24 VDC, 438 mA
24 VDC, 438 mA
24 VDC, 250 mA
24 VDC, 542 mA
RAC Current
0.5 A
0.75 A
0.87 A
1 A
2
2
to 3.31 mm
)
2
) wire leads, color coded
MFG.
Model Number
8210A107 (097617-005D coil) 1/2" NPS, 5/8" orifice,
24 VDC
8210G207 (238310 coil) 1/2" NPS, 1/2" orifice
8211A107 (097617-005D coil) 24VDC
ASCO
HV2628571 (23810 coil) N.C. 1/2" NPS, 1/2" orifice
HV2648581 (23810 coil) N.O. 1/2" NPS, 1/2" orifice
R8210A107 (097617-005D coil) 1/2" NPS, 5/8" orifice
T8210A107 (097617-005D coil) 1/2" NPS, 5/8" orifice
ECH Electrical Control Head (551201)
Pyro-
Explosion-Proof Electric Actuator (570147)
Chem
Removable Electric Actuator (570209) 0.2 A
6
NAC Current
0.845 A
1.28 A
1.5 A
1.71 A
S4010-0003-5 6/2013