Module and Accessories Selection Information (Continued)
Field Installed Optional Modules
Model
Description
4190-8001*
TrueInsight Remote Service Gateway Module and Programming Selection
TrueInsight Remote Service Gateway Module Installation Kit; includes
4190-6106 *
module and harness; configured for dynamic IP address operation unless
ordered with 4190-4016
TrueInsight Remote Service Gateway Module for fixed IP Addressing; optional, select if application will use fixed IP
4190-4016 *
address
Network Interface Card; Modular Network Interface; requires two media modules (below).
4007-9810
Wired Media Module
4007-9813
Fiber Optic Media Module
4007-9814
* Refer to data sheet S4100-0063 for additional TrueInsight Service Gateway details
Batteries
Model
Capacity
Battery Mounting Details
2081-9272
6.2 Ah
2081-9274
10 Ah
12 V Batteries for cabinet mounting; select one battery model per system standby requirements; order quantity of
two; to be wired in series for 24 VDC
2081-9288
12.7 Ah
2081-9275
18 Ah
2081-9287
25 Ah
For remote mount in Battery Box 4009-9801
2081-9271
33 Ah
For remote mount in Battery Box 4009-9802
Battery Accessories
Model
Color
Capacity
For up to 25 Ah
4009-9801
Beige
batteries
For up to 33 Ah
4009-9802
Beige
batteries
Accessories
Model
Description
2080-9047
DACT cable, 14 ft (4.3 m) long, RJ45 plug one end, spade lugs on the other; order one per phone line connection required
2975-9812
Red semi-flush box trim; 1
2975-9813
Platinum semi-flush box trim; 1
Series resistor for WSO, IDCs (N.O. water flow and tamper on same circuit, wires after water flow and before tamper) 470 Ω,
2081-9031
1 W, encapsulated, two 18 AWG leads (0.82 mm
addressable initiating zones.
4081-9002
3.3 kΩ, 1 W end-of-line resistor for Class B non-addressable initiating zones
4081-9018
10 kΩ, 1 W end-of-line resistor harness for non-addressable NACs

General Specifications

Input Power
4007ES Hybrid Power
Supply Output Ratings
Special Application Non-Addressable
Appliances
Regulated 24 DC Non-Addressable Appliances
Battery Charger
Ratings
(sealed lead-acid
batteries)
Select media cards as required; mounts to
4007-9810 NIC; Class B or Class X operation
Dimensions
16 ¼" W x 13 ½" H x 5 ¾" D
(413 mm x 343 mm x 146 mm)
25 ¾" W x 20 ¾" H x 4 ⅛" D
(654 mm x 527 mm x 105 mm)
7
" (37 mm) wide, four corners and trim pieces for top, bottom, and sides
16
7
" (37 mm) wide, four corners and trim pieces for top, bottom, and sides
16
120 VAC Input 2 A maximum @ 102 to 132 VAC, 50/60 Hz
240 VAC Input 1 A maximum @ 204 to 264 VAC, 50/60 Hz
Power Supply
Including module currents and auxiliary power outputs;
Output Rating
6 A total
3 A each for Special Application Appliances
NAC Ratings
2 A each for Regulated 24 DC Appliances
Auxiliary Power Tap 2 A maximum, 24 VDC nominal (19.5 to 31.1 VDC)
Simplex horns, strobes, and combination horn/strobes and speaker/strobes
(contact your Simplex product representative for compatible appliances)
Power for other UL listed appliances; use associated external synchronization
modules where required
UL and ULC listed for battery charging of 6.2 Ah up to 33 Ah (batteries larger
Battery capacity range
than 18 Ah require a remote battery cabinet)
Temperature compensated, dual rate, recharges depleted batteries within 48
Charger characteristics
hours per UL Standard 864; to 70% capacity in 12 hours per ULC Standard
and performance
S527
Batteries for remote mounting; see battery cabinet details
below
Description
External battery cabinet without charger, with locking solid
door and battery harness; for close-nippled mounting to fire
alarm control panel cabinet
2
), 2 ½" L x 1 ⅜" W x 1" H (64 mm x 35 mm x 25 mm). This is for non-
6
Supv.
Required
62 mA
Selection
30 mA (with no
cards installed)
55 mA
25 mA
Output switches to
battery backup
during mains AC
failure or brownout
conditions
S4007-0001-10 1/2017
Alarm
73 mA
30 mA
55 mA
25 mA