Specifications - Simplex TrueAlarm 4008-9102 Manual

Fire alarm control panels for idnet addressable devices and addressable smoke detection

Advertisement

Specifications

(Refer to Installation Instructions 579-716 for additional information)
Input Current, Standard
AC Input
Input Current with
Expansion Power Supply
Power Supply Output
Battery Charger
Notification Appliance Circuits (NACs) (NOTE: Total DC current = 3 A maximum per power supply)
General Rating
Special Application Rating = 2 A per NAC
Strobe synchronization is UL listed across all
four system NACs for these 4906 Series
appliances
Regulated 24 VDC Rating = 1.5 A per NAC
NOTE: Maximum strobe load on main power
supply or expansion power supply is 1.35 A
per power supply (2.7 A total); remainder of
power supply rating is available for other
loading
Standard Circuit Ratings (NOTE: Total DC current = 3 A maximum per power supply)
Auxiliary Power Output
Standard Auxiliary Relay Outputs
Wiring Connections
IDNet Communications
Quantity
Suppression
Wire Size
Unshielded twisted pair (UTP)
Wire Types
Shielded twisted pair (STP)
Distance from Control Panel to Farthest
Device
Total Wire Length Allowed With "T" Taps for
Class B Wiring
Total Capacitance Allowed
Annunciator Communications
Quantity Supported
Wiring Size and Type
Wiring Distances
Line Matching Resistor
Suppression
Option Module Ratings
Expansion Relay
Module 4008-9802
Environmental Ratings
Operating Temperature Range
Operating Humidity Range
Input Voltage
120 VAC, 60 Hz; 220/230/240 VAC, 50/60 Hz, auto-select
2 A maximum @ 120 VAC input; 1.5 A maximum @ 240 VAC input
4 A maximum @ 120 VAC input; 3 A maximum @ 240 VAC input
3 A maximum @ 24 VDC in alarm
Temperature compensated charger is rated for up to 25 Ah per UL 864; up to
12.7 Ah per ULC-S527
2 A maximum @ 24 VDC, per NAC; available as Class A or Class B;
Class B end-of-line resistor = 10 k, ½ W; Model 4081-9008 (P/N 733-894)
Simplex 4901 Series (horns) and 4906 Series Multi-Candela non-addressable
strobes, horn/strobes, and speaker/strobes (contact your Simplex product
representative for compatible appliances)
Power for other UL listed appliances; use associated external synchronization
modules where required
500 mA maximum @ 24 VDC
Relay 1
Programmable operation
Relay 2
Trouble operation
Terminals rated for 18 AWG to 12 AWG (0.82 mm
Up to 200 addressable devices (see list on page 4)
For wiring external to building, use Overvoltage Protector 2081-9044 at each end
of the connection; refer to data sheet S2081-0016 for details
18 AWG (0.82 mm
Acceptable for most applications; not for use with wiring in conduit with either NAC
or AC power wiring (or similar)
Shielded wire may provide protection from unexpected sources of interference and
may be required for some applications; review system with your local Simplex
product supplier
Up to 4000 feet (1219 m) with 125 devices; 32 
Up to 2500 feet (762 m) with 200 devices; 51 
Up to 10,000 ft (3 km)
0.6 µF (600 nF)
Up to four annunciator modules per panel (see page 4 for details)
See description for IDNet wiring above
Up to 4000 ft (1219 m); 0.58 µF (580 nF) maximum capacitance; 35  max.
Bus-Style Wiring
"T-Tap" Wiring
Up to 10,000 ft (3048 m) total wiring; up to 2500 ft (762 m) to farthest device
Bus-Style Wiring
Connect one at panel and one at end of line
"T-Tap" Wiring
Connect one at panel and one at farthest device
Use 2081-9044 Overvoltage Protectors where wiring leaves and enters a building
(refer to data sheet S2081-0016)
Contact Ratings
2 A @ 30 VDC, 0.35 power factor; jumper selectable as N.O. or N.C.
Wiring
Terminals rated for 18 AWG to 12 AWG (0.82 mm
32° to 120°F (0° to 49° C)
Up to 93% RH, non-condensing @ 100.4° F (38° C) maximum
Contacts rated 2 A @ 30 VDC, 0.35 power factor;
jumper selectable as N.O. or N.C.
2
)
5
2
2
to 3.31 mm
)
100 , ½ W; 4081-9011;
(part number 733-974)
2
2
to 3.31 mm
)
S4008-0001-8 8/2012