General Specifications
Input Power
120 VAC Models; 4 A maximum @ 102 to 132 VAC, 60 Hz
Power Supplies; SPS,
XPS, and RPS
220-240 VAC Models; 2 A maximum @ 204 to 264 VAC, 50/60 Hz; with taps for 220/230/240 VAC
120 VAC Models; 4 A maximum @ 102 to 132 VAC, 60 Hz
100 W Amplifier Power
Supplies
220-240 VAC Models; 2 A maximum @ 204 to 264 VAC, 50/60 Hz; with taps for 220/230/240 VAC
Amplifier Ratings
Built-in Tones
Flex-35 Amplifiers:
4100-1361
4100-1362
4100-1363
4100-1364
Flex-50 Amplifiers:
4100-1312
4100-1313
4100-1326
4100-1327
100 W Amplifiers and Backup Amplifiers:
4100-1314, 4100-1316, 4100-1318,
4100-1320, 4100-1322, 4100-1324;
4100-1328, 4100-1330, 4100-1332,
4100-1334, 4100-1336, 4100-1338
Total Amplifier Power per Cabinet
Audio Controller Ratings
4100-9620, 4100-1210 Analog = 225 mA supervisory
Current
Requirements
4100-9621, 4100-1311 Digital = 85 mA supervisory
Analog Riser Distance
Digital Riser Distance; 18 AWG
unshielded, twisted pair (UTP) required,
except as noted (refer to Installation
Instructions 574-844)*
Firefighter Telephone Distance Ratings
Distance
Battery Charger, System and Remote Power Supply (sealed lead-acid batteries)
Battery capacity range
Charger characteristics and performance
Environmental
Operating Temperature Range
Operating Humidity Range
Additional 4100ES Data Sheet Reference
Subject
Basic Panel Modules
LED/Switch Modules
MINIPLEX Transponders
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited.
© 2012 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
500 Hz horn tone operated at temporal pattern, provided when amplifiers are separated from
audio controller
Input Voltage
Supervisory Current
Alarm Current
@ full output power
Input Voltage
Supervisory Current
Alarm Current
@ full output power
Supervisory Current
Alarm Current
@ full output power
300 W maximum
Up to 10,000 ft (3048m) total with 18 AWG (0.82 mm
Up to 2500 ft (762 m) from 4100-1311 Digital Controller to 4100-0622 Digital Audio Riser or
4100-1341 MCC Digital Riser Interface; up to 2500 ft (762 m) between 4100-0622 Digital
Audio Riser Modules or 4100-1341 MCC Digital Riser Interfaces (signal is reformatted and
repeated); wire runs over 100 ft (30 m) require UTP wire
* NOTE: Wire runs of 100 ft (30 m) or less require shielded twisted pair wire (STP)
7500 ft (2286 m) distance to farthest phone, 18 AWG shielded twisted pair (STP)
UL listed for battery charging of 6.2 Ah up to 110 Ah (110 Ah batteries require a remote battery
cabinet); ULC listed for charging up to 50 Ah batteries
Temperature compensated, dual rate, recharges depleted batteries within 48 hours per UL
Standard 864, to 70% capacity in 12 hours per ULC Standard S527
32° to 120°F (0° to 49° C)
Up to 93% RH, non-condensing @ 90° F (32° C) maximum
Data Sheet
Subject
S4100-0031
Network Display Unit (NDU)
S4100-0032
Enclosures
S4100-0035
Remote Annunciators
Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA
www.simplexgrinnell.com
19 to 35 VDC from adjacent power supply
425 mA with power stage supervised
85 mA in low power mode
5.5 A with continuous horn tone
1.64 A average, with temporal pattern horn
19 to 35 VDC from adjacent power supply
425 mA with power stage supervised
85 mA in low power mode
5.55 A with continuous horn tone
2.27 A average, with temporal pattern horn
400 mA (analog); 220 mA (digital) with power stage supervised
85 mA in low power mode
9.6 A with continuous horn tone
3.8 A average, with temporal pattern horn
Add for local speaker in alarm: 75 mA min. volume;
190 mA half volume; 333 mA full volume;
Add microphone current separately; Supv.= 2.4 mA;
Active = 30 mA
2
Data Sheet
Subject
S4100-0036
InfoAlarm Comm. Center
S4100-0037
Remote Battery Charger
S4100-0038
Remote Firefighter Phones
Use this value for power
supply loading
Use this value for battery
backup reference
Use this value for power
supply loading
Use this value for battery
backup reference
Use this value for battery
backup reference
) shielded twisted pair (STP)
Data Sheet
S4100-0045
S4081-0002
S2084-0001
S4100-0034-12 3/2012