Aux-Rpo: User Remote Power Off (Rpo); User Line Wiring; Aux Port Terminal Assignments - Xantrex XW4024 230 50 Installation Manual

Xw hybrid inverter/charger
Table of Contents

Advertisement

AUX-RPO: User Remote Power Off (RPO)

User Line Wiring

AUX Port Terminal Assignments

975-0384-01-02
Connecting JU-2 (AUX-RPO) and JU-3 (AUX-COM) terminals together through
an external switch (normal open contact) provides the system shut off function if
the switch is closed.
The external switch, if pressed, overrides the control provided from the front
panel.
If the external switch is cleared (not pressed), the system can be enabled back
from the front panel.
Select an external switch with normal open contact. Consult your system
designer or qualified technician for specific installation instructions.
Use twisted pairs of #24 AWG to #12 AWG (0.5 mm
Carefully route the wires away from high power load cables to minimize noise
effects on signal integrity.
Table 2-7 User Connector Terminals and Functions
Pin
Reference
JU-1
AUX+12V
JU-2
AUX-RPO
JU-3
AUX-COM
JU-4
Not
Operational
JU-5
Not
Operational
This manual for use by qualified personnel only
Name
Function
+12 V User
+12 VDC Voltage source: 250 mA
Voltage Supply
maximum
Remote Power
Remote Power Off Logic Level:
Off
Active Low. Activating this signal
shuts down system operation.
Common Ground
Return Common Ground
Reference
Reference for 12V, Remote Power
Off signals.
Not Operational
Not Operational
Not Operational
Not Operational
Step 4: Wiring the Inverter
2
2
to 2.5 mm
) for connections.
2–27

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xw4548 230 50Xw6048 230 50

Table of Contents