Inverter/Charger Installation
Inverter Load
Sub-Panel (230 V)
230 V
_AC Wiring (all)-EU.vsd/AC Wiring to SubPanel /April 10, 2008
Actual wiring and grounding requirements may vary.
_AC Wiring-to-subpanel-EU.vsd May 3, 2010
© 2007 Xantrex Technology Inc .
Figure 2-14 Wiring the Xantrex XW Inverter/Charger to the Inverter Load Sub-Panel and Utility Grid
2–24
To connect the inverter to the main utility panel:
1. See Figure 2-14. Connect the neutral wire from the main utility panel to the
inverter GRID (AC1) neutral terminal.
2. Connect the AC LIVE wire from the main utility panel to the inverter GRID
(AC1) L terminal.
To connect the inverter to the AC generator:
1. See Figure 2-15. Connect the neutral wire from the generator breaker or
disconnect to the inverter GEN (AC2) neutral terminal.
2. Connect the AC LIVE wire from the generator breaker or disconnect to the
inverter GEN (AC2) L terminal.
AC OUT
AC IN
AC IN
L
N
L
N
L
N
AC
GEN
GRID
(AC2)
LOAD
(AC1)
Hybrid Inverter /Charger
LIVE
N
IN
LIVE OUT
G
LOAD
AC
Neutral
AC LIVE
Groun
This manual for use by qualified personnel only
AC
AC IN
AC IN
OUT
N
L
L
L
N
AC
GRID
GEN
(AC1)
(AC2)
Primary System Ground
Torque all inverter terminal block connections
according to Table 2-4 on page 2–13.
The Neutral-to-Ground bond, which
is provided in the utility grid system,
may be located upstream.
Main Utility Panel
N
N
G
975-0384-01-02