Make sure nothing is between the terminal
surface and the battery cable lug
3/8-15 x 5/8" bolt (supplied)
Figure 2-10 Battery Cable Connection
975-0384-01-02
Important: The next step is the last cable connection. A spark is normal when
this connection is made.
7. Connect the other end of the cable to the NEGATIVE (–) terminal on the
battery.
8. Use a wrench to tighten the bolt to the required torque.
9. Attach the DC terminal covers.
Battery cable lug
Flat washer
Split-ring lock washer
CAUTION: Damage to Equipment
Do not put anything between the battery cable lug and the terminal surface.
Overheating of the terminal may occur. Do not apply any type of antioxidant
paste until after the battery cable wiring is tightened. The same applies for all DC
connections. Do not over-tighten; observe all recommended torque values.
CAUTION: Reverse Polarity Damage
Before making the final DC connection or closing the DC breaker or disconnect,
check cable polarity at both the battery and the inverter/charger. Positive (+)
must be connected to positive (+). Negative (–) must be connected to
negative (–).
Reverse polarity damage is not covered by warranty.
This manual for use by qualified personnel only
Step 4: Wiring the Inverter
Terminal surface
Shrink-wrap to
color-code the cable
Copper compression lug
2–17