Mantel Requirements; Install Example - Build-Out (Dog-House) W Hor. Term; Finalizing The Installation - Travis Industries 864 ST Installation Manual

Travis industries built-in direct vent fireplace
Hide thumbs Also See for 864 ST:
Table of Contents

Advertisement

Finalizing the Installation

Mantel Requirements

The illustration below details mantel clearances and maximum mantel depth.
Any material that protrudes more than 3/4" from the non-combustible facing is considered a mantel
and must meet the mantel requirements.
Maximum Mantel Depth (b)
0" 1" 2" 3" 4" 5" 6" 7" 8" 9" 10"11" 12"
18+"
17"
16"
15"
14"
13"
12"
11"
10"
Mantel
9"
Height
8"
7"
Above
6"
Face (a)
5"
4"
3"
2"
1"
0"
Examples:
• If you wish to have a 8" deep mantel, it must be at least 6-3/4" above the fireplace face (43-1/2" above the base).
• If you wish to have a mantel 8" above the fireplace face, it must be no deeper than 9".
© Travis Industries
Mantel
(combustible or non-combustible)
b
a
36-3/4"
Base of the Fireplace
4071126
(for qualified installers only)
Combustible mantel columns (legs) that
protrude more than 3/4" from the glass
frame must meet the sidewall clearance. If
they protrude 3/4" or less, they must meet
the facing clearance 2-1/4" from the glass
frame).
Non-combustible mantel columns do not
have a minimum clearance.