Mantel Requirements

Use the table below to determine the maximum mantel depth allowed. The mantel depth (measured from the
non-combustible facing) must fall within the shaded portion of the table.
Any material above the fireplace that protrudes more than 3/4" (19mm) from the non-combustible facing is
considered a mantel and must meet the mantel requirements.
47" (1194mm)
46" (1169mm)
45" (1143mm)
Mantel
44" (1118mm)
Height
43" (1093mm)
Above
42" (1067mm)
Base (a)
41" (1042mm)
40" (1016mm)
39" (991mm)
38" (966mm)
37" (941mm)
36" (916mm)
35" (890mm)

Mantel Column Clearances

Combustible mantel columns (legs) require a 0" (0mm) clearance to the side of the fireplace (they must
be to the side of the fireplace).
Non-combustible mantel columns do not have a minimum clearance.