Finalizing the Installation

Side Vent Configuration with Vertical Termination

The termination must fall
within the shaded area
shown in the chart. Use the
indicated restrictor and
diffuser positions.
Up to four elbows (45° or
90°) may be used.
Only one horizontal elbow
may be used.
This is considered a horizontal
elbow (it does not matter
whether it turns right or left).
It may be a 90° or 45° elbow.
© Travis Industries
(for qualified installers only)
40' (max)
35 feet
30 feet
25 feet
20 feet
15 feet
10 feet
5 feet
0 feet
H2
H1
4071126
Exhaust Restrictor # 4
Intake Restrictor # 2
Diffuser Position # 1
Exhaust Restrictor # 2
Intake Restrictor # 1
Diffuser Position # 1
Horizontal length is calculated by adding
both lengths of horizontal run
(Horizontal Length = H1 + H2).
This is considered a
vertical elbow
25
40' (max)
35 feet
30 feet
25 feet
20 feet
15 feet
10 feet
5 feet
0 feet
100-01195_000