Appendix 2 Instructions for UL and cUL compliance

(Conforming standard UL 508C, CSA C22.2 No.14)
(1) Installation
This inverter is a UL / cUL Listed, enclosed type device with a suitably rated enclosure.
Design an enclosure so that the inverter surrounding air temperature, humidity and atmosphere satisfy the
specifications.
(Refer to page 136.)
Precaution
The bus capacitor discharge time is 10 minutes. Before starting wiring or inspection, switch power off, wait for more
than 10 minutes, and check for residual voltage between terminal P/+ and N/- with a meter etc., to avoid a hazard of
electrical shock.
Wiring protection
For installation in the United States, branch circuit protection must be provided in accordance with the National
Electrical Code and any applicable provincial codes.
For installation in Canada, branch circuit protection must be provided in accordance with the Canadian Electrical Code
and any applicable provincial codes.
Provide the appropriate UL and cUL listed Class RK5, Class T or Class L type fuse or UL489 molded case circuit
breaker (MCCB) that is suitable for branch circuit protection in accordance with the table below.
Note, the Class L fuses can be used if the applicable current rating is larger than 600 A.
FR-F720-
K
Rated fuse voltage(V)
Fuse
Without power factor
improving reactor
maximum
allowable
With power factor
improving reactor
rating (A)*
Molded case circuit breaker
(MCCB)
Maximum allowable rating (A)*
FR-F720-
K
Rated fuse voltage(V)
Fuse
Without power factor
improving reactor
maximum
allowable
With power factor
improving reactor
rating (A)*
Molded case circuit breaker
(MCCB)
Maximum allowable rating (A)*
FR-F740-
K
Rated fuse voltage(V)
Fuse
Without power factor
improving reactor
maximum
allowable
With power factor
improving reactor
rating (A)*
Molded case circuit breaker
(MCCB)
Maximum allowable rating (A)*
FR-F740-
K
Rated fuse voltage(V)
Fuse
Without power factor
improving reactor
maximum
allowable
With power factor
improving reactor
rating (A)*
Molded case circuit breaker
(MCCB)
Maximum allowable rating (A)*
* Maximum allowable rating by US National Electrical Code.
Exact size must be chosen for each installation.
0.75
1.5
2.2
3.7
5.5
15
20
30
40
15
20
20
30
15
15
20
35
75
90
110
240V or more
500
600
700
700
800
1000
0.75
1.5
2.2
3.7
5.5
6
10
15
20
6
10
10
15
15
15
15
15
75
90
110
132
160
250
300
350
400
500
350
450
500
650
800
7.5
11
15
18.5
240V or more
60
80
150
175
200
50
70
125
150
200
50
70
100
125
175
7.5
11
15
18.5
480V or more
30
40
70
80
90
25
35
60
70
90
25
40
50
70
80
185
220
250
280
500V or more
600
700
800
900
800
1000 1200 1200 1200 1600 1600 2000 2000 2500
22
30
37
45
225
300
350
400
200
250
300
350
200
250
350
400
500
22
30
37
45
110
150
175
200
100
125
150
175
100
125
175
200
250
315
355
400
450
500
1000 1100 1200 1350 1500 1800
55
500
400
55
250
200
560
153