Appendix 2 Instructions for UL and cUL Compliance

(Conforming standard UL 508C, CSA C22.2 No.14)
(1) Installation
This inverter is a UL / cUL Listed, enclosed type device with a suitably rated enclosure.
Design an enclosure so that the inverter ambient temperature, humidity and atmosphere satisfy the specifications.
(Refer to page 117.)
Wiring protection
For installation in the United States, branch circuit protection must be provided in accordance with the National
Electrical Code and any applicable provincial codes.
For installation in Canada, branch circuit protection must be provided in accordance with the Canadian Electrical Code
and any applicable provincial codes.
Provide the appropriate UL and cUL listed Class RK5, Class T or Class L type fuse or UL489 molded case circuit
breaker (MCCB) that is suitable for branch circuit protection in accordance with the table below.
FR-F740-
-EC
Rated fuse voltage(V)
Without power
Fuse
factor improving
Maximum
reactor
allowable
With power factor
rating (A)*
improving reactor
Molded case circuit breaker
(MCCB)
Maximum allowable rating (A)*
FR-F740-
-EC
Rated fuse voltage(V)
Without power
Fuse
factor improving
Maximum
reactor
allowable
With power factor
rating (A)*
improving reactor
Molded case circuit breaker
(MCCB)
Maximum allowable rating (A)*
* Maximum allowable rating by US National Electrical Code at SLD rating.
Exact size must be chosen for each installation.
(2) Wiring of the power supply and motor
For wiring the input (R/L1, S/L2, T/L3) and output (U, V, W) terminals of the inverter, use the UL Listed copper, stranded
wires (rated at 75°C) and round crimping terminals. Crimp the crimping terminals with the crimping tool recommended
by the terminal maker.
(3) Short circuit ratings
• Model 01160 or less
Suitable For Use in A Circuit Capable Of Delivering Not More Than 100kA rms Symmetrical Amperes, 528V Maximum.
• Model 01800 or more
Suitable For Use in A Circuit Capable Of Delivering Not More Than 100kA rms Symmetrical Amperes, 550V Maximum.
00023 00038 00052 00083 00126 00170 00250 00310 00380 00470 00620 00770 00930 01160
6
10
15
20
6
10
10
15
15
15
15
20
01800 02160 02600 03250 03610 04320 04810 05470 06100 06830 07700 08660 09620 10940 12120
300
350
400
500
450
500
600
800
480V or more
30
40
70
80
25
35
60
70
30
40
60
70
500V or more
600
700
800
900
1000 1100 1200 1350 1500 1800 2000
900
1000 1200 1200 1200 1600 1600 2000 2000 2500 3000
90
110
150
175
200
90
100
125
150
175
90
100
150
175
225
250
200
250
133