Parameter list
Parameter
134
PID differential time
PID deviation limit
553
PID signal
554
operation selection
Output interruption
575
detection time
Output interruption
576
detection level
Output interruption
577
cancel level
PID display bias
C42
coefficient
(934)
PID display bias
C43
(934)
analog value
PID display gain
C44
coefficient
(935)
PID display gain
C45
analog value
(935)
The parameter number in parentheses is the one for use with the parameter unit (FR-PU04/FR-PU07).
90
Incre
Initial
Name
ments
Value
0.01s
9999
0.1%
9999
1
0
0.1s
1s
0.01Hz
0Hz
0.1%
1000% 900 to 1100%
0.01
9999
0.1%
20%
0.01
9999
0.1%
100%
Range
Description
For deviation lamp input, time (Td) required
for providing only the manipulated variable
0.01 to
for the proportional (P) action. As the
10.00s
differential time increases, greater
response is made to a deviation change.
9999
No differential control.
Y48 signal is output when the absolute
0 to 100.0%
value of deviation amount exceeds the
deviation limit value.
9999
No function
Select the operation to be performed at the
detection of upper, lower, and deviation
0 to 3,
limit for the measured value input. The
10 to 13
operation for PID output suspension
function can be selected.
If the output frequency after PID operation
remains lower than the Pr. 576 setting for
0 to 3600s
longer than the time set in Pr. 575, the
inverter stops operation.
9999
Without output interruption function
Set the frequency at which the output
0 to 400Hz
interruption processing is performed.
Set the level (Pr.577 - 1000%) to release the
PID output interruption function.
Set the coefficient on bias side (minimum)
0 to 500.00
of terminal 4 input.
9999
Displayed in %.
Set the converted % on bias side
0 to 300.0%
(minimum) current /voltage of terminal 4
input.
Set the coefficient on gain side (maximum)
0 to 500.00
of the terminal 4 input.
9999
Displayed in %.
Set the converted % on gain side
0 to 300.0%
(maximum) of current/voltage of terminal 4
input.
All
Para
Para
para
meter
meter
meter
copy
clear
clear
: enabled
× : disabled
×
×
×
×