Parameter list
Parameter
Life alarm status
255
display
Inrush current limit
256
circuit life display
Control circuit
257
capacitor life display
Main circuit
258
capacitor life display
Main circuit
259
capacitor life
measuring
260
Refer to Pr.72.
Power failure stop
261
selection
Deceler
ate the
motor to
a stop at
instanta
Subtracted
neous
262
frequency at
power
deceleration start
failure
Subtraction starting
263
frequency
Power-failure
264
deceleration time 1
Power-failure
265
deceleration time 2
Power failure
266
deceleration time
switchover frequency
267
Refer to Pr.73.
268
Refer to Pr.52.
269
Parameter for manufacturer setting. Do not set.
299
Refer to Pr.57, Pr. 58.
96
Incre
Initial
Name
ments
Value
1
0
1%
100%
1%
100%
1%
100%
1
0
1
0
0.01Hz
3Hz
0.01Hz
60Hz
0.1/
5s
0.01s
0.1/
9999
0.01s
0.01Hz
60Hz
Range
Description
Displays whether the control circuit capacitor,
main circuit capacitor, cooling fan, and each
(0 to 15)
parts of the inrush current limit circuit has
reached the life alarm output level or not.
Displays the deterioration degree of the
(0 to 100%)
inrush current limit circuit. Reading only
Displays the deterioration degree of the
(0 to 100%)
control circuit capacitor. Reading only
Displays the deterioration degree of the
(0 to 100%)
main circuit capacitor. Reading only
The value measured by Pr. 259 is displayed.
Start measuring the main circuit capacitor life.
Switch the power supply on again and
0, 1
check the Pr. 259 setting. Measurement is
complete if the setting is "3". Set the
deterioration degree in Pr.258.
Operation at
restoration
undervoltage
during power
or power
failure
deceleration
Coasts to a stop -
0
Coasts to a stop
Decelerates
Decelerates to
1
to a stop
a stop
Decelerates
Accelerates
2
to a stop
again
Decelerates
Decelerates to
21
to a stop
a stop
Decelerates
Accelerates
22
to a stop
again
Normally operation can be performed with the
initial value unchanged. But adjust the
0 to 20Hz
frequency according to the magnitude of the
load specifications (moment of inertia, torque).
When output frequency ≥ Pr.263
Decelerate from the speed obtained from
0 to 120Hz
(output frequency - Pr.262).
When output frequency < Pr.263
Decelerate from output frequency
Decelerate from the speed obtained from
9999
(output frequency - Pr.262).
0 to 3600/
Set a deceleration slope down to the
360s
frequency set in Pr.266.
0 to 3600/
Set a deceleration slope below the
360s
frequency set in Pr.266.
9999
Same slope as in Pr.264
Set the frequency at which the deceleration
0 to 400Hz
slope is switched from the Pr.264 setting to
the Pr.265 setting.
Para
meter
copy
At power
Deceleration
time to a stop
failure
Depends on
Pr. 262 to Pr.
266 settings
Depends on
Pr. 262 to Pr.
266 settings
Automatically
adjusts the
deceleration
time
Automatically
adjusts the
deceleration
time
All
Para
para
meter
meter
clear
clear
: enabled
× : disabled
×
×
×
×
×
×
×
×
×
×
×
×