Mitsubishi Electric F700 Instruction Manual page 94

Hide thumbs Also See for F700:
Table of Contents

Advertisement

Parameter
Name
PU communication
117
station number
PU communication
118
speed
PU communication
119
stop bit length
PU communication
120
parity check
Number of PU
121
communication
retries
PU communication
122
check time interval
PU communication
123
waiting time setting
PU communication
124
CR/LF selection
Communication
EEPROM write
342
selection
PU mode operation
command source
551
selection
Incre
Initial
Range
ments
Value
Specify the inverter station number.
Set the inverter station numbers when two
1
0
0 to 31
or more inverters are connected to one
personal computer.
Set the communication speed.
The setting value × 100 equals the
48, 96,
1
192
communication speed.
192, 384
For example, the communication speed is
19200bps when the setting value is "192".
Stop bit length
0
1bit
1
1
1
2bit
10
1bit
11
2bit
0
Without parity check
1
2
1
With odd parity check
2
With even parity check
Set the permissible number of retries at
occurrence of a data receive error.
0 to 10
If the number of consecutive errors
exceeds the permissible value, the inverter
1
1
will come to trip.
If a communication error occurs, the
9999
inverter will not come to trip.
0
No PU connector communication
Set the communication check time interval.
If a no-communication state persists for
0.1s
9999
0.1 to 999.8s
longer than the permissible time, the
inverter will come to trip.
9999
No communication check
Set the waiting time between data
0 to 150ms
transmission to the inverter and response.
1
9999
9999
Set with communication data.
0
Without CR/LF
1
1
1
With CR
2
With CR/LF
Parameter values written by communication
0
are written to the EEPROM and RAM.
1
0
Parameter values written by
1
communication are written to the RAM.
Select the RS-485 terminals as the PU
1
operation mode control source.
1
2
Select the PU connector as the PU
2
operation mode control source.
Parameter list
Para
meter
copy
Description
data length
8bit
8bit
7bit
7bit
All
Para
para
meter
meter
clear
clear
: enabled
× : disabled
4
87

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-f720Fr-f740

Table of Contents