Appendix 3 Instructions for UL and cUL compliance

(Conforming standard UL 508C, CSA C22.2 No.14)
(1) General Precaution
The bus capacitor discharge time is 10 minutes. Before starting wiring or inspection, switch power off, wait for
more than 10 minutes, and check for residual voltage between terminal P/+ and N/- with a meter etc., to avoid a
hazard of electrical shock.
(2) Environment
Before installation, check that the environment meets following specifications.
Surrounding Air
Temperature *1
Ambient humidity
Storage temperature
Ambience
Altitude, vibration
*1
Surrounding Air Temperature is a temperature measured at a measurement position in an enclosure. Ambient Temperature is a temperature
outside an enclosure.
2
*2
2.9m/s
or less for the 160K or higher
(3) Installation
This inverter is UL-listed as a product for use in an enclosure.
Design an enclosure so that the inverter surrounding air temperature, humidity and atmosphere satisfy the
specifications. (Refer to page 175.)
Wiring protection
For installation in the United States, Class RK5, Class J, Class CC, Class L, Class T or any faster acting fuses or UL
489 Molded Case Circuit Breaker (MCCB) must be provided, in accordance with the National Electrical Code and any
applicable local codes.
For installation in Canada, Class RK5, Class J, Class CC, Class L, Class T or any faster acting fuses or UL 489 Molded
Case Circuit Breaker (MCCB) must be provided, in accordance with the Canada Electrical Code and any applicable
provincial codes.
FR-A720-
K
Rated fuse voltage(V)
Without power
Fuse
factor improving
maximum
reactor
allowable
With power
rating (A)*
factor improving
reactor
Molded case circuit
breaker (MCCB)
maximum allowable
rating (A)*
FR-A720-
K
Rated fuse voltage(V)
Without power
Fuse
factor improving
maximum
reactor
allowable
With power
rating (A)*
factor improving
reactor
Molded case circuit
breaker (MCCB)
maximum allowable
rating (A)*
Constant torque: -10°C to + 50°C (non-freezing)
90%RH or less (non-condensing)
-20°C to + 65°C
Indoors (No corrosive and flammable gases, oil mist, dust and dirt.)
2
Below 1000m, 5.9m/s
or less*2 at 10 to 55Hz (directions of X, Y, Z axes)
0.4
0.75
1.5
2.2
15
20
30
40
15
20
20
30
15
15
20
25
75
90
240V or more
600
700
700
800
Enclosure
Inverter
5cm
Measurement
position
3.7
5.5
7.5
11
240V or more
60
80
150
175
50
70
125
150
40
60
80
110
Measurement
position
5cm
5cm
15
18.5
22
30
200
225
300
350
200
200
250
300
150
175
225
250
37
45
55
400
500
500
350
400
500
350
400
500
193